Start-Up - Neptronic SKE4-E Series Installation Instructions And User Manual

Steam humidifier
Hide thumbs Also See for SKE4-E Series:
Table of Contents

Advertisement

Start-Up

1. Proceed to start-up the humidifier, as follows:
Start-up
2. Check the location of the Airflow switch in the system and its operation by
Safety Test
3. Turn off the humidifier by pressing and holding the Power
4. Conduct a drain cycle by pressing and holding the Drain button
Drain and
Reset
5. Once the drain cycle is complete, restart the humidifier by pressing and
6. Reset the Airflow switch if needed.
End
7. The humidifier is now ready for normal operation.
www.neptronic.com
a) With the humidifier front access open, ensure that the manual drain valve
is closed.
b) Turn on the humidifier by pressing and holding the Power button
seconds. Verify that the controller Status Display LED is blue.
c) Verify that there is a humidity demand displayed on the LCD screen of the
humidifier.
d) Ensure that the water supply valve connected to the humidifier is turned
on and that water is flowing directly to the humidifier water supply inlet.
Ensure that the water shut off valve is turned off.
e) Verify the water level as water is filling the evaporation chamber by using
the control panel to access the WaterLevel setting located in the Physical
IO sub-menu of the General menu. Ensure that there are no water leaks
along the water line.
f)
Once the evaporation chamber has been filled, observe the system for
water and steam leaks during several minutes of operation.
stopping the fan. With no air movement, the humidifier should automatically
stop.
seconds.
seconds. Ensure that the evaporation chamber has been emptied.
holding the Power
button for 3 seconds.
SKE4-E Steam Humidifier
Installation Instructions and User Manual
for 3
button for 3
for 3
Page | - 61 -