Water Supply Connections - Neptronic SKE4-E Series Installation Instructions And User Manual

Steam humidifier
Hide thumbs Also See for SKE4-E Series:
Table of Contents

Advertisement

Water Supply Connections

Water Inlet Specifications:
Inlet water pressure: 1.7 to 4.8 bars
o
Maximum temperature: 30°C
o
DN15 standard copper water line connection or DN20 PEX pipe line
o
Water Supply Line Installation:
Connect a DN15 water supply braided hose (by others) to the male threaded part
o
of the pipe.
In order to facilitate servicing, install a shutoff valve (not supplied) in the water supply line
close to the humidifier.
It is recommended to install a standard water strainer in the water supply line.
It is recommended to install a water hammer arrestor, in order to absorb hydraulic shock
and minimize water hammer when the fill valve closes.
Main Drain:
Connect 3/4 (DN20)
compression fitting to
hydraulic pipe
www.neptronic.com
Water Supply Inlet:
Connect to male threaded
part of pipe
Illustration 31 - Water Supply and Drain Connections
SKE4-E Steam Humidifier
Installation Instructions and User Manual
Pan Drain:
Connect 1/2 (DN15)
elbow fitting to
hydraulic pipe
Page | - 31 -