Positioning

Ensure that the front panel, the left side (plumbing compartment) and the right side
(electrical compartment) are accessible in order to permit servicing.
Leave a clearance of at least 1.2 m to the front panel and 0.3 m on the left and right sides
of the humidifier.
Leave a clearance of at least 0.5 m on top of the humidifier.
For models SKE4-E05 to E80:
Mount the humidifier at a minimum height of 0.6 m above floor level.
o
Leave a clearance of at least 0.25 m under the humidifier for installation of water
o
supply, drain piping and electrical connections.
For models SKE4-E90 to E120:
These models are designed to be installed directly on the floor. Adjustable legs
o
are provided in order to ensure proper level.
Provide a level, solid foundation and ensure that the floor beneath the humidifier
o
is water proof to withstand any water spillage during servicing or in the event of a
problem.
www.neptronic.com
Installation Instructions and User Manual
Illustration 6 - Positioning the Humidifier
SKE4-E Steam Humidifier