Water supply installation must conform to local codes and regulations.
Any installation work must be carried out by suitably qualified personnel.
Water Inlet
Neptronic
Specifications
de-ionized and de-mineralized water.
Maximum water supply pressure: 70 to 480kPa
Minimum water temperature: +4˚C
Maximum water temperature: +40˚C
Water Supply
To facilitate servicing, it is recommended to install a shut off valve (not supplied) in
Line Installation
the water line, within 1m of the humidifier.
It is recommended to install a water hammer arrestor, in order to absorb hydraulic
shock and minimize water hammer when the fill valve closes.
Stage 3 – Water Supply Installation
®
SKE-XL Humidifier is designed to be used with mains, reverse osmosis,
Model
SKE90
SKE100
SKE110
SKE120
Gasket
SKE-XL
120 mm
Water Inlet connection
(Illus. 13)
13
SKE-XL BACnet Steam Humidifier
Installation Instructions and User Manual
Water inlet
Connection size
Ø 15 mm
Feed Water supply line
¼ turn Shut off Valve
Gasket
Flexible Hose