DIN-Rail Mounting

The aluminum DIN-rail attachment plate should already be fixed to the back
panel of the Ethernet Switch when you take it out of the box. If you need to
reattach the DIN-rail attachment plate, make sure the stiff metal spring is
situated towards the top, as shown in the figures below.
STEP 1:
Insert the top of the DIN-Rail into
the slot just below the stiff metal
spring.
To remove the Ethernet Switch from the DIN-Rail, simply reverse Steps 1 and 2
above.

ATEX Information

1. Certificate number DEMKO 11
ATEX150193X
2. Ambient range (-40°C ≤ Tamb ≤ 75°C)
3. Certification string (Ex nA nL IIC T4)
4. Standards covered (EN60079-0:2006, EN60079-15:2005)
5. The conditions of safe usage:
 The Ethernet Communication Devices are to be mounted in an IP54
enclosure and used in an area of not more than pollution degree 2 as
defined by IEC60664-1.
 Use a conductor wire of size 0.2 mm or greater.
 Conductors suitable for use in an ambient temperature of 100°C must be
used for the Power Supply Terminal.
 Provisions shall be made, either in or external to the apparatus, to
prevent the rated voltage from being exceeded by more than 40% due to
transients disturbances.
STEP 2:
The DIN-Rail attachment unit will snap
into place as shown below.