Weidmuller IE-SW-VL16 Series Hardware Installation Manual

Unmanaged fast ethernet switch valueline

Advertisement

Quick Links

Unmanaged Fast Ethernet Switch
ValueLine
IE-SW-VL16 Series

Hardware Installation Guide

8th Edition, March 2018
1243330000/07/04.18
Important note:
This document and additional product information can be
downloaded using following link:
http://www.weidmueller.com
► Select Product Catalogue
Select „Active Industrial Ethernet "
Select „ValueLine unmanaged Switches "
Select Product model
Click and expand section „Downloads "
Download needed software or documentation
Copyright Notice
Copyright  2018 Weidmüller Interface GmbH & Co. KG
All rights reserved.
Reproduction without permission is prohibited.

Advertisement

Table of Contents
loading

Summary of Contents for Weidmuller IE-SW-VL16 Series

  • Page 1: Hardware Installation Guide

    Unmanaged Fast Ethernet Switch ValueLine IE-SW-VL16 Series Hardware Installation Guide 8th Edition, March 2018 1243330000/07/04.18 Important note: This document and additional product information can be downloaded using following link: http://www.weidmueller.com ► Select Product Catalogue Select „Active Industrial Ethernet “ Select „ValueLine unmanaged Switches “...
  • Page 2: Package Checklist

    Ethernet network. IE-SW-VL16 series is available with an operating temperature range of 0 to 60°C or optional with extended operating temperature range from -40 to 75°C. The devices are designed to withstand a high degree of vibration and shock.
  • Page 3: Panel Layout

    Panel Layout IE-SW-VL16(T)-16TX Grounding screw Terminal block for power input P1/P2 Heat dissipation orifices DIP Switches Power input PWR1 LED Power input PWR2 LED Fault LED 10/100BaseT(X) Port TP port’s 100 Mbps LED 10. TP port’s 10 Mbps LED 11. Article number 12.
  • Page 4 Panel Layout IE-SW-VL16(T)-14TX-2SC Grounding screw Terminal block for power input P1/P2 Heat dissipation orifices DIP Switches Power input PWR1 LED Power input PWR2 LED Fault LED 10/100BaseT(X) Port TP port’s 100 Mbps LED 10. TP port’s 10 Mbps LED 11. Article number 12.
  • Page 5 Panel Layout IE-SW-VL16(T)-14TX-2ST Grounding screw Terminal block for power input P1/P2 Heat dissipation orifices DIP Switches Power input PWR1 LED Power input PWR2 LED Fault LED 10/100BaseT(X) Port TP port’s 100 Mbps LED 10. TP port’s 10 Mbps LED 11. Article number 12.
  • Page 6: Mounting Dimensions

    Mounting Dimensions Units: mm (inch) DIN-Rail Mounting The aluminum DIN-rail attachment plate should already be fixed to the back panel of the Ethernet Switch when you take it out of the box. If you need to reattach the DIN-rail attachment plate, make sure the stiff metal spring is situated towards the top, as shown in the figures below.
  • Page 7: Wall Mounting (Optional)

    Wall Mounting (optional) For some applications, you will find it convenient to mount the Ethernet switch on the wall, as shown in the following figures. STEP 1: Remove the aluminum DIN-Rail attachment plate from the switch rear panel, and then attach the wall mount plates as shown in the diagram at the right.
  • Page 8: Atex Information

    ATEX Information Certificate number DEMKO 11 ATEX 150194X Ambient range: -40°C ≤ Tamb ≤ +75°C for models with suffix of “-T”; 0°C ≤ Tamb ≤ +60°C for models without suffix of “-T” Certification string: Ex nA nC IIC T4 Gc Rated Cable Temperature: ≧...
  • Page 9: Wiring Requirements

    Wiring Requirements WARNING Do not disconnect modules or wires unless the power supply has been switched off or the area is known to be non-hazardous. The devices may only be connected to the supply voltage shown on the type plate. The devices are designed for operation with a Safety Extra-Low Voltage.
  • Page 10: Wiring The Alarm Contact

    Grounding Ethernet Switch Grounding and wire routing help limit the effects of noise due to electromagnetic interference (EMI). Run the ground connection from the ground screw to the grounding surface prior to connecting devices. A 4 mm² conductor must be used when a connection to the external grounding screw is utilized.
  • Page 11: Wiring The Redundant Power Inputs

    Wiring the Redundant Power Inputs Both power inputs can be connected simultaneously to live DC power sources. If one power source fails, the other live source acts as a backup, and automatically supplies the Ethernet Switch’s power needs. The top two contacts and the bottom two contacts of the 6-contact terminal block connector on the Ethernet Switch’s top panel are used for the Ethernet Switch’s two DC inputs.
  • Page 12: Communication Connections

    Communication Connections The models of IE-SW-VL16 series have 14 or 16 10/100BaseT(X) Ethernet ports, and 2 or 0 (zero) 100 BaseFX multimode (SC/ST-type connector) fiber ports. 10/100BaseT(X) Ethernet Port Connection The 10/100BaseT(X) ports located on Ethernet Switch’s front panel are used to connect to Ethernet-enabled devices.
  • Page 13: Dip Switch Settings

    Laser Beam. DIP Switch Settings IE-SW-VL16 Series DIP Switches The default setting for each DIP Switch is OFF. The following table explains the effect of setting the DIP Switches to the ON positions.
  • Page 14: Led Indicators

    LED Indicators The front panel of the Ethernet Switch contains several LED indicators. The function of each LED is described in the table below. Color State Description Power is being supplied to power input PWR1. PWR1 AMBER Power is not being supplied to power input PWR1.
  • Page 15 Switches of IE-SW-VL16 series have an address table that can hold up to 4K node addresses, which makes it suitable for use with large networks.
  • Page 16: Specifications

    Specifications Technology IEEE 802.3 for 10BaseT, Standards IEEE 802.3u for 100BaseT(X) and 100Base FX, IEEE 802.3x for Flow Control Forward and Filtering 148,810 pps (100Mbit), 14,881 pps (10Mbit) Rate Packet Buffer Memory 1.25 Mbit Store and Forward, with IEEE802.3x full duplex, Processing Type back pressure flow control MAC-address Table...
  • Page 17 Environmental 0 to 60°C (32 to 140°F) Operating Temperature -40 to 75°C (-40 to 167°F) for -T models Storage Temperature -40 to 85°C (-40 to 185°F) Ambient Relative 5 to 95% (non-condensing) Humidity Regulatory Approvals Safety UL 508, UL 60950-1, EN 60950-1 UL/cUL Class I, Division 2, Groups A, B, C, and D;...