E96-216 ® ® Configuration Port Module (IMCPM01) Process Control and Automation Solutions from Elsag Bailey Group...
Page 2
The information contained in this document is subject to change without notice. Elsag Bailey, its affiliates, employees, and agents, and the authors and contributors to this publication specif- ically disclaim all liabilities and warranties, express and implied (including warranties of merchantability and...
Page 3
System engineers and technicians should read this manual before installing and operating the CPM module. A module SHOULD NOT be put into operation until this instruction is read and understood. ® INFI 90 and Network 90 are registered trademarks of Elsag Bailey Process Automation. I-E96-216A...
Page 4
® List of Effective Pages Total number of pages in this instruction is 18, consisting of the following: Page No. Change Date Preface Original List of Effective Pages Original iii through v Original 1-1 through 1-4 Original 2-1 through 2-2 Original 3-1 through 3-3 Original...
Page 5
Safety Summary GENERAL Equipment Environment WARNINGS All components, whether in transportation, operation, or storage must be in a noncorrosive environment. Electrical Shock Hazard During Maintenance Disconnect power or take precautions to insure that contact with energized parts is avoided when servicing. Sommaire de Securite AVERTISSEMENT Environment de l'Equipement...
Tuning Terminal (CTT01/CTT02) and the INFI 90/Network 90 system. This manual explains the purpose, operation and maintenance of the Configuration Port Module (IMCPM01). It explains han- dling cautions and steps for installing the CPM. Figure shows the INFI 90/Network 90 communication levels and where the CPM module is within these levels.
Maintenance has a schedule for maintaining the module. Support Services explains how to order parts. It also explains other areas of support that Bailey Controls provides. INTENDED USER 1 - 2 I-E96-216A...
INTRODUCTION GLOSSARY Term Definition Configuration Tuning Terminal; a hand held terminal providing a local means for sys- tem, configuration, monitoring, tuning and diagnostics. Configuration A control strategy with function blocks. Module Mounting Unit; a card cage that provides electrical and communication sup- port for INFI 90 modules.
® SPECIFICATIONS Occupies one slot in a standard INFI 90 Module Mounting Unit Mounting (MMU). Fuse Type: 0.5 Amp 250 Volt Bailey P/N 194776A15000 ® Littlefuse 312.500 Buss AGC-1/2 ™ Power Consumption Power consumed is that of the CTT0_. CTT02 uses 85 mA at...
CPM (P1) and the module bus as shown in Figure 1-1. Figure shows the schematic of a CPM. CONNECTS TO CTT IMCPM01 TP35834A Figure 2-1. Configuration Port Module INPUTS AND OUTPUTS Digital signals to and from the CTT are +5 VDC. Section 3 explains the module connections.
(MMU BACKPLANE) CTT CONNECTOR MOUNTED ON FACEPLATE TP35832A Figure 2-2. IMCPM01 Input/Output Circuit LOGIC POWER Logic power (+5 VDC) for the CTT circuits connects through the top 12-pin card edge connector (P1) shown in Figure 2-1. MODULE BUS The module bus provides a 83.3 kilobaud peer-to-peer commu- nication link capable of supporting up to 32 drops.
1. Examine the hardware when you receive it to verify that it has not been damaged in transit. 2. Notify the nearest Bailey Controls Sales Office of any ship- ping or handling damage. 3. File a claim for any damage with the company that handled the shipment.
Cable Connections The CPM connects to the CTT with the five foot flexible cord permanently attached to the CTT (see Figure 3-1). MODULE IMCPM01 TP35833A Figure 3-1. IMCPM01 Cable Connections and Termination WIRING CONNECTIONS AND CABLING 3 - 2 I-E96-216A...
Page 16
INSTALLATION FUSING The CPM has a 0.5 Amp on-board fuse. Use only a 0.5 Amp 250 Volt fuse Bailey P/N 194776A15000, Littlefuse P/N 312.500, Bussman AGC-1/2 or equivalent. PRE-OPERATING ADJUSTMENTS You do not have to make any adjustments to the CPM before operating.
Page 17
SECTION 4 - TROUBLESHOOTING INTRODUCTION This section explains the error indications and corrective actions for the Configuration Port Module (IMCPM01). ERROR INDICATIONS AND CORRECTIVE ACTION The CTT01/02 receives power from module mounting unit. If the CTT loses power, follow the steps in this section. There are no active electrical components on the CPM.
TROUBLESHOOTING ® CONNECTS TO CTT IMCPM01 TP35834A Figure 4-1. IMCPM01 Fuse Location MODULE PIN CONNECTIONS The CPM module has one connection point for external signals and power (P1). Table shows the P1 pin connections. Table 4-1. P1 Pin Connections Connection...
SECTION 5 - MAINTENANCE INTRODUCTION The Configuration Port Module (IMCPM01) requires limited maintenance. This section contains a schedule to maintain the CPM. MAINTENANCE SCHEDULE Do the tasks in Table at the noted times. Table 5-1. Maintenance Schedule Task Interval Clean and tighten all power and Every 6 months or during plant shut- grounding connections.
Page 20
SECTION 6 - SUPPORT SERVICES INTRODUCTION Bailey Controls is ready to help in the use and repair of its products. Contact your nearest sales office to make requests for sales, repair and maintenance contracts. REPLACEMENT PARTS AND ORDERING INFORMATION When making repairs at your plant, order parts from a Bailey Controls sales office.