Single Step Ramp Mode; Ramp Busy - Infinite Pasternack PE11S100 Series User Manual

Table of Contents

Advertisement

User Manual | PE11S100X Series Synthesizer
Figure 3. 2-Way Sweep Control via Trigger

4.4.3 Single Step Ramp Mode

Single-step mode is selected by setting ramp_singlestep
(Reg 14
h<6>). In this mode, a trigger is required
for each step of the ramp. Single-step mode will function with either one-way or two-way ramps. The
operation of single-step mode for a one-way ramp is shown graphically in
Figure
4.
Figure 4. Single Step Ramp Mode

4.4.4 Ramp Busy

In all types of sweeps, ramp_busy will indicate an active sweep and will stay high between the first and nth
ramp step. The ramp_busy signal may be monitored one of two ways: