Figure 9-7 Replacing a BPS
Step 3 Install the new BPS.
----End

9.1.5 Replacing a Monitoring Unit

9.1.5.1 Replacing an SMU02S

Prerequisites
Procedure
Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD
gloves.
Step 2 Disconnect the communications cable from the SMU02S panel.
Step 3 Push the locking latch leftwards.
Step 4 Pull the handle outwards and remove the SMU02S.
Figure 9-8 Removing the SMU02S
Step 5 Place the new SMU02S in the slot, push the locking latch leftwards, and pull out the handle.
Issue 02 (2020-03-17)
An ESD wrist strap, ESD gloves, ESD box or bag, and cabinet door key are available.
The new SMU02S is intact.
Copyright © Huawei Technologies Co., Ltd.
9 Parts Replacement
131