Trane MWC518 Installation & Operation Manual page 18

Advanced multi-split system cassette indoor unit
Hide thumbs Also See for MWC518:
Table of Contents

Advertisement

Unit Installation
Ceiling
Figure 13.
Explanation
Over 100mm
Figure 14.
2.
[Water injection method]
(drain off the water in the gutter via this outlet)
Figure 15.
18
Less than 300mm
Drainage hose
(accessory)
The inclination of supplied drainage hose shall not exceed 75mm, allowing the drainage
socket not have to bear additional external force.
If several drainage pipes converge, then perform the installation by following the
procedures below.
Drainage hose
(accessory)
Selected confl uent drainage pipe to be sized to operating capacity to the
unit
Check if the water drains smoothly at the end of installation.
Slowly inject 600cc water via air outlet or inspection hole to check the drainage.
Check the drainage in the cooling condition after installation of electrical circuits.
Service drainage outlet
(with rubber plug)
Over 100mm
Roof
1-1.5m
Drainage lift pipe
Clamp (accessory)
Drainage pipe
<Inject water via the
inspection hole>
Plastic spray can
(its tube shall be about 100mm in length)
<Inject water at the air outlet end>
Hanger bracket
Less than 280mm
220mm
T-joint Confluent
drainage pipe
Inspection hole cover
Inspection hole
AMS-SVX02A-EN