Vertiv Liebert iCOM Installer/User Manual page 172

Intelligent communication and monitoring for liebert mini-mate variable capacity 3 ton
Hide thumbs Also See for Liebert iCOM:
Table of Contents

Advertisement

Table B.4 Service Menu Alarm Settings by Line ID (continued)
Line
ID
S297
S298
S2A2
S2A3
S2A4
S2A5
S2A6
S2A7
164
Parameter
Range
Name
Event Enabled
Disabled Enabled
Event: REDUCED
MESSAGE WARNING ALARM
ECO AIRFLOW
Event Delay Time
10 - 9999 sec
(sec)
Event Enabled
Disabled Enabled
Event: ECO HI
MESSAGE WARNING ALARM
TEMP OVERRIDE
Event Delay Time
10 - 9999 sec
(sec)
Event Enabled
Disabled Enabled
Event: TEMP CTRL
MESSAGE WARNING ALARM
SENSOR FAIL
Event Delay Time
10 - 9999 sec
(sec)
Event Enabled
Disabled Enabled
Event: HIGH DEW
MESSAGE WARNING ALARM
POINT
Event Delay Time
10 - 9999 sec
(sec)
Event Enabled
Disabled Enabled
Event: LOW DEW
MESSAGE WARNING ALARM
POINT
Event Delay Time
10 - 9999 sec
(sec)
Event Enabled
Disabled Enabled
Event: HI DEW
MESSAGE WARNING ALARM
POINT SENSOR A
Event Delay Time
10 - 9999 sec
(sec)
Event Enabled
Disabled Enabled
Event: LOW DEW
MESSAGE WARNING ALARM
POINT SENSOR A
Event Delay Time
10 - 9999 sec
(sec)
Event Enabled
Disabled Enabled
MESSAGE WARNING ALARM
Event Delay Time
10 - 9999 sec
(sec)
Default
Description
Setting
Enabled
WARNING
10 sec
Enabled
Eco High Temperature Override
WARNING
10 sec
Enabled
Temperature Control Sensor Fail
ALARM
30 sec
Enabled
High Dew Point
WARNING
30 sec
Enabled
Low Dew Point
WARNING
30 sec
Enabled
High Dew Point Sensor A
WARNING
30 sec
Enabled
Low Dew Point Sensor A
WARNING
30 sec
High Remote Sensor
Enabled
WARNING
30 sec
Low Remote Sensor
Vertiv™ | Liebert® iCOM™ Installer/User Guide

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents