Table B.4 Service Menu Alarm Settings by Line ID (continued)
Line
Parameter
ID
Name
Warning Activates
S208
Alarm Relay
K11 (WA Relay)
S209
Active On
K11(WA Relay) and
S210
AL Relay
Water Alarm Shuts
Down Unit
S211
Water Alarm Hum
Fill Down
Loss of Flow
S21A
Compressor Timer
Loss of Flow
S21B
Threshold
Supply Sensor
Alarms Enable
S213
Supply Sensor
Alarms Init Delay
High Supply
Temperature
S214
Low Supply
Temperature
Dew Point Alarms
Enable
S215
Dew Point Alarms
Init Delay
High Dew Point
S216
Low Dew Point
Default
Range
Setting
No Yes
Yes
0 = Dehum
1 = Warning
2 = Emergency Pwr
Warning
3 = Freecooling
4 = FC Start
Direct Reverse
Direct
No
No
Yes
No
No
Yes
0 - 180 sec
0 sec
0 - 100 %
0.1
Disabled
Disabled
Enabled
10 - 9999 sec
90 sec
34 - 210 °F
75 °F
1.0 - 99.0 °C
34 - 210 °F
1.0 - 99.0 °C
50 °F
Disabled
Disabled
Enabled
10 - 9999 sec
90 sec
34 - 210 °F
59 °F
1.0 - 99.0 °C
34 - 210 °F
1.0 - 99.0 °C
39 °F
Description
When set for Yes, a Warning event type will
activate the Alarm Relay in addition to an Alarm
event type.
The Warning Relay (WA Relay) can be activated
for different purposes; during a Call of
Dehumidification, during a Warning event type,
when unit is on Emergency Power and a
Customer Input Alarm is configured for
Emergency Pwr, during Freecooling, or during
Freecooling (FC) Start.
Determines whether the K11 (WA Relay) is Direct
or Reverse acting.
The controller can be configured to shut the
following down during an active Water Alarm:
Shutdown the entire unit
Shutdown Humidification
operation
Allows setting a maximum pump down time
during a loss of flow condition to prevent causing
a high-pressure alarm due to pump down with no
water/glycol flow to the condenser; hidden
unless pump down is enabled; applies only to
water/glycol cooled systems
Sets the threshold for call for cooling (CFC) loss
of flow.
Enables or disables the supply sensor alarms. If
the unit is not equipped with a supply
temperature sensor, then this parameter will
show Disabled. A user may also select the time
delay before the alarm will become active.
Sets the high and low supply temperature
threshold that the alarms will be triggered at.
Enables or disables the Return Air Dew Point
alarm. Dew Point alarms can be enabled with
any humidity control type. Dew point alarms
may be used with or without humidification or
dehumidification options selected. A user may
adjust the time delay before the alarm is
activated.
Sets the high/low depoint threshold.