Condair HumiLife RH Series Installation Manual

Condair HumiLife RH Series Installation Manual

Hide thumbs Also See for HumiLife RH Series:

Advertisement

READ AND SAVE THESE INSTRUCTIONS
Installation Manual
Condair HumiLife
– The proven steam solution
Condair RH
Humidification and Evaporative Cooling

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HumiLife RH Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Condair HumiLife RH Series

  • Page 1 READ AND SAVE THESE INSTRUCTIONS Installation Manual Condair HumiLife – The proven steam solution Condair RH Humidification and Evaporative Cooling...
  • Page 2: Cautions And Warnings

    Condair does not accept any liability for installations of humidity equipment installed by unqualified personnel, or the use of parts, components, or equipment that are not authorized or approved by Condair.
  • Page 3: Table Of Contents

    Installing the Steam Distributor Mounting the Humidifier Installing the Steam Line Installing the Condensate Return Water Supply Connection Drain Connection Electrical Connection Controls Connecting to Condair HumiLife Downloading Condair HumiLife Connecting to Condair HumiLife Condair RH Contents | 3 2594947_B_EN_2005_Condair-RH_IM...
  • Page 4: Receiving And Storage

    Storage, Packaging, and Transportation Storage Store the Condair HumiLife RH in its original packaging inside a protected area that meets the following requirements until it is installed, or if it needs to be stored for an extended period of time: Room temperature: 41 to 104 °F (5 to 40 °C)
  • Page 5: Product Overview

    18. Drain pan 5. Steam hose 12. Condensate return cap 19. Drain valve 6. Steam hose clamp 13. Fill cup 20. Fill valve 7. Steam cylinder 14. Hose clip 21. Adapter, quick connect Condair RH Product Overview | 5 2594947_B_EN_2005_Condair-RH_IM...
  • Page 6: Description

    Description The Condair HumiLife RH is a residential steam humidifier designed by Condair. It is designed to provide steady, clean humidification for the home, and is designed to connect to a supply air duct. The humidifier may be mounted directly onto the duct, or remotely with connected steam hoses and distributor.
  • Page 7: Specifications

    Model Fuse Freq. A (MCA) A (MOCP) gpd / kg/h / lb/h 11 / 1.8 / 3.9 110-120 Condair RH - Phase 1, 19 / 3.0 / 6.7 12.0 NAP, 22 50/60 Hz 22 / 3.6 / 7.8 220-240 Dimensions Ø...
  • Page 8: Installation Instructions

    5. Electrical disconnect switch (not 7. High limit sensor (optional) supplied) 3. On/Off wall humidistat * 8. Fan enable/activation * only an on/off humidistat (not supplied) OR RH sensor (supplied) should be installed. Installation Instructions | 8 Condair RH 2594947_B_EN_2005_Condair-RH_IM...
  • Page 9 5. Drain (not supplied) 2. Water shut off valve (not supplied) 4. On/Off wall humidistat * 6. Electrical disconnect switch (not supplied) * only an on/off humidistat (not supplied) OR RH sensor (supplied) should be installed. Condair RH Installation Instructions | 9 2594947_B_EN_2005_Condair-RH_IM...
  • Page 10: Installing The Steam Distributor

    Installing the Steam Distributor The Condair HumiLife RH can be installed directly onto the duct system or remotely, with the installation of a steam distributor (including steam lines) to the duct. The installation of the steam distributor (and steam line) will determine the appropriate location for mounting the humidifier.
  • Page 11 Do NOT over tighten hose clamps at the steam outlet. Max torque: 12 in·lbs(1.36 Nm). Ensure the steam line material is Condair-supplied, otherwise copper or stainless steel. Ensure the steam line out of the humidifier is vertical 6 in (15 cm) min. before any bends.
  • Page 12: Mounting The Humidifier

    Allow clearances required for plumbing and electrical connections. Clearance dimensions shown are for reference only and are the minimum required for maintenance of the humidifier. Consult local and national codes before final location and installation. Condair does not accept responsibility for installation code violations.
  • Page 13 A. Ensure the unit is level. 4. Through the inside of the humidifier, insert and tighten a screw into the lower mounting hole B. Tighten the top screw at A. Condair RH Installation Instructions | 13 2594947_B_EN_2005_Condair-RH_IM...
  • Page 14: Installing The Steam Line

    Figure 11 - Installing the Steam Line and Steam Distributor Installing the Steam Line: 1. Connect the steam hose to the humidifier and route it to the steam distributor, outer diameter 1 in (25 mm). Secure with clamps. 14 | Installation Instructions Condair RH 2594947_B_EN_2005_Condair-RH_IM...
  • Page 15: Installing The Condensate Return

    3. Inside the humidifier, remove the cap from the fill cup and attach the condensate line to the condensate port. Secure with a clamp. Figure 12 - Removing the Plumbing Cover and Installing the Condensate Return Line 1. Condensate return port, Ø 0.31 in (8 mm) 2. Fill cup Condair RH Installation Instructions | 15 2594947_B_EN_2005_Condair-RH_IM...
  • Page 16: Water Supply Connection

    39 - 86 °F (4 - 30 °C), cold water Conductivity: 125 - 1250 µS/cm Other: Water shut-off valve installed before the humidifier (for service). Installed according to national and local plumbing code. 16 | Installation Instructions Condair RH 2594947_B_EN_2005_Condair-RH_IM...
  • Page 17: Drain Connection

    Drain Connection Drain Requirements The Condair HumiLife RH produces hot water during operation. Upon normal drainage, the drain water is automatically cooled to 140 °F (60 °C). IMPORTANT! Drain water may reach high temperatures 212 °F (100 °C) in cases where the supply water is not cold, or obstructed.
  • Page 18: Electrical Connection

    Ensure that adequate power is available to carry full humidifier amp draw, as indicated on the specification label. A dedicated external fused disconnect may be installed between the humidifier and the circuit breaker. Do NOT use the neutral wire as a ground. 18 | Installation Instructions Condair RH 2594947_B_EN_2005_Condair-RH_IM...
  • Page 19: Controls

    Condair controls are available as accessories and can be ordered with the purchase of the humidifier. If the controls were not ordered with the humidifier, they must be purchased from Condair, or be supplied by others. A relative humidity (duct) sensor is supplied with the unit. Requirements:...
  • Page 20 B1/B2: Air proving switches, safety high limit humidistat, or external contact. Jumper, use if air proving switch or furnace fan not installed. C1: Fan activation, connect to HVAC system F1: Fuse 1AT (5x20 mm) F2: Fuse 16AT, SPT (5x20 mm) Q1: External disconnect or breaker 20 | Installation Instructions Condair RH 2594947_B_EN_2005_Condair-RH_IM...
  • Page 21: Connecting To Condair Humilife

    Connecting to Condair HumiLife Once the humidifier is mounted, and steam, water, drain, and wiring connections have been established, you can turn on the unit and control it with the Condair HumiLife app on your mobile device. Downloading Condair HumiLife Use your phone's camera or QR scanner to go to Google Play (Android) or the App Store (iOS).
  • Page 22 Consult the dealer or an experienced radio/TV technician for help. Warranty Condair Inc. and/or Condair Ltd.(hereinafter collectively referred to as THE COMPANY), warrant for a period of five years from the date of purchase by the customer, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted, are free from defects in material and workmanship.