Automatic battery tests run according to "periodic battery test", unless
disabled. During the test, the UPS transfers to Battery mode and
discharges the batteries for 10 seconds under the existing load.
The "UPS on Battery" notice and the "Battery Low" alarm do not activate
during a battery test.
NOTE: For automatic battery tests to run:
The "Automatic Battery Support Tests" setting must be enabled.
The UPS must be in Normal mode, with no active alarms.
The batteries must be fully charged.
The bypass voltage must be acceptable.
To pass the battery test, the battery voltage must remain above the
threshold value during discharge.
Description
Adjustable parameters
Ambient
[enabled], [disabled]
temperature
If enabled, UPS alarm when
high alarm
ambient temperature >40°C
EPO
[normally open], [normally
operation
closed]
Normally open means UPS makes
a shutdown by a closing input
state.
Normally closed means UPS
makes a shutdown by an opening
input state.
Setting only available in UPS
stand-by mode.
Reset
[no], [yes]
Cumulative
If "no", no action.
Consumption
If "yes", the Cumulative
kWh
Consumption kWh value is
cleared and the date and time
stamp for this statistic is set to
the current date and time.
Battery limit
5h,6h,...14h,15h,16h,...999h,
time
disabled
Default "14h" means when work
on battery mode for more than 14
37
Presetting
enabled
normally
closed
no
14h
EN