AEG Protect D Series User Manual page 36

Power solutions
Hide thumbs Also See for Protect D Series:
Table of Contents

Advertisement

36
6.
Set the other load segment if applicable.
Load segment On/Off commands issued through the Control menu
overrules the settings for load segments.
Description
Start w/o
mains
Battery Saving
Mode
Site Wiring
Fault Alarm
External
battery
modules
Charger output
voltage / cell
Battery Charge
capability % to
Restart
Automatic
battery
support tests
Periodic
Battery Tests
Adjustable parameters
[enabled], [disabled]
cold Start
[disabled], [10%], [20%], ...[100%]
On battery operation the UPS
output is turned off as soon as the
battery capacity is below the
selected level.
[enabled], [disabled]
[0], [1], ..., [9]
Float charging voltage per battery
cell 2.21V, 2.22V, 2.23V, 2.24V,
2.25V, 2.26V,
2.27V, 2.28V, 2.29V, 2.30V, 2.31V
[0%], [10%], [20%], ...[100%]
When enabled, automatic restart
is made when the battery charge
state reaches the selected level.
If set 0, the feature is disabled.
[enabled], [disabled]
[daily], [weekly], [monthly]
Presetting
enabled
disabled
disabled
0
2.28V
0
enabled
weekly