Priming Features; Setting Priming Features; Disabling Priming With An Automation System - Pentair INTELLIFLO Installation And User Manual

Variable speed pump
Table of Contents

Advertisement

Priming features are only accessible if priming
is "Enabled".
1. Press
.
2. Use
arrow to scroll to "Priming" and press
3. The factory default is set to priming "Enabled". To
disable, press
4. Press
if you have changed the setting - this
will save the selection.
5. Press the
arrow - the screen will read "Max
Priming Time".
6. To change from factory default, press
cursor will highlight.
7. Use the
or
from 1 minute to 30 minutes.
8. Press
to save.
9. Press the
arrow - the screen will read "Priming
Range". Default is "5".
10. Press
to change the priming range. The
cursor will highlight the number.
11. Use the
or
10. Increasing the number allows the drive to detect
12. Press
to save.
13. Press the
arrow - the screen will read "Priming
Delay". Default is 20 seconds.
14. Press
to change the priming delay time.
15. Use the
or
second to 10 minutes.
Increasing the time causes the pump
to stay in the priming mode longer.
1. Disable priming on automation control system.
3. Disable priming on pump.
.
arrows to change the time
arrows to change from 1 to
arrows to change from 1
16. Press
17. Press
When the IntelliFlo
an automation control system, (IntelliTouch
or SunTouch
Control Systems),
®
If priming is enabled on start up, the pump responds to its
internal settings
The
automation control system.
If the pump is connected to an automation control system
and priming is not desired,
1. Disable the priming feature on the automation control
system at the load center or using an IntelliTouch or
EasyTouch system remote. (Refer to the automation
control system user's guide for additional information).
2. Temporarily disconnect the RS-485 communication
cable.
3. Open the lid to the control panel to disable priming
on the pump. Press
scroll and select "Priming", then select "Disabled" (the
factory default is set to "Enabled"). Press
the menu.
4. Once priming is disabled, reinstall the RS-485
communication cable.
2. Disconnect the RS-485 communication cable.
4. Reinstall the RS-485 communication cable.
INTELLIFLO
Variable Speed Pump Installation and User's Guide
®
to save the setting.
to exit.
Variable Speed Pump is connected to
®
responding to commands from an
, use the
15
, EasyTouch
®
®
buttons to
to exit