Application and functions

1.5 Compatibility with previous product

1.5
Compatibility with previous product
1.5.1

Extended functionality compared with previous product

Replacing a module
The CP (6GK7443-5DX05-0XE0 and 6GK7443-5DX05-0XE1) described here with firmware
version V7.0 can be used as a replacement for the following predecessors of the CP 443-5
Extended:
● 6GK7 443-5DX00-0XE0
● 6GK7 443-5DX01-0XE0
● 6GK7 443-5DX02-0XE0
● 6GK7 443-5DX03-0XE0
● 6GK7 443-5DX04-0XE0
Firmware loader - reduced loading time with "FWL_FAST_LOAD"
To load new firmware, use only the new function for fast loading.
To do this, select the following entry for the interface parameter assignment of your PC/PG
in the firmware loader:
CPxxx(FWL_FAST_LOAD)
By using this function, the time required for loading firmware is reduced significantly
compared with the old function.
Note
CPxxx (FWL) cannot be used
The setting CPxxx(FWL) in the interface parameter assignment cannot be used with this CP
type.
Note
PROFIBUS
Download the firmware only via the PROFIBUS interface of the CP. To download the
firmware, you can use the following:
• PROFIBUS connecting cable 6ES7 901-4BD00-0XA0
• PROFIBUS cable with a maximum length of 200 m
The use of an MPI cable is not permitted!
24
CP 443-5 Extended
Manual, 11/2018, C79000-G8976-C162-09