Siemens SIMATIC NET CP 443-5 Extended Manual page 39

For use in a simatic s7-400 automation system
Table of Contents

Advertisement

ATEX
The CP meets the requirements of the EC directive 2014/34/EU "Equipment and Protective
Devices for Use in Potentially Explosive Atmospheres".
ATEX approval:
● II 3 G Ex nA IIC T4 Gc
Type Examination Certificate: KEMA 03 ATEX1125 X
Applied standards:
– EN 60079-0 - Explosive atmospheres - Part 0: Equipment - General requirements
– EN 60079-15 - Explosive atmospheres - Part 15: Equipment protection by type of
● II 3 G Ex ec IIC T4 Gc
Type Examination Certificate: DEKRA 18ATEX0027 X
Applied standards:
– EN 60079-0 - Explosive atmospheres - Part 0: Equipment - General requirements
– EN 60079-7 - Explosive Atmospheres - Part 7: Equipment protection by increased
The current versions of the standards can be seen in the EC Declaration of Conformity, see
above.
ATEX approval: II 3 G Ex nA IIC T4 Gc
The conditions must be met for the safe deployment of the CP according to the section
Notes on use in hazardous areas according to ATEX / IECEx (Page 30).
You should also note the information in the document "Use of subassemblies/modules in a
Zone 2 Hazardous Area" that you will find on the Internet at the following address:
Link: (https://support.industry.siemens.com/cs/ww/en/view/78381013)
EMC
Until 19.04.2016 the CP meets the requirements of the EC Directive 2014/30/EU
"Electromagnetic Compatibility" (EMC directive).
Applied standards:
● EN 61000-6-4
Electromagnetic compatibility (EMC) - Part 6-4: Generic standards - Emission standard
for industrial environments
● EN 61000-6-2
Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity for
industrial environments
CP 443-5 Extended
Manual, 11/2018, C79000-G8976-C162-09
protection 'n'
safety 'e'
Approvals
39

Advertisement

Table of Contents
loading

Table of Contents