Quick Guide
Parameter
Parameter 8-01 Control Site
Parameter 8-30 Protocol
Parameter 8-32 Baud Rate
Parameter 20-00 Feedback 1 Source
Parameter 20-01 Feedback 1
Conversion
Table 1.15 Closed-loop Applications Set-up
Changes made
Changes Made lists all parameters changed from default
settings.
•
The list shows only parameters which have been
changed in the current edit set-up.
•
Parameters which have been reset to default
values are not listed.
•
The message Empty indicates that no parameters
have been changed.
To change parameter settings
1.
To enter the Quick Menu, press [Menu] until
indicator in display is placed above Quick Menu.
▲
▼
2.
Press [
] [
] to select quick guide, closed-loop
set-up, compressor set-up, or changes made, then
press [OK].
▲
▼
3.
Press [
] [
] to browse through the parameters in
the Quick Menu.
4.
Press [OK] to select a parameter.
▲
▼
5.
Press [
] [
] to change the value of a parameter
setting.
6.
Press [OK] to accept the change.
7.
Press either [Back] twice to enter Status, or press
[Menu] once to enter Main Menu.
MG18M202
Quick Guide
Option
[0] Digital and ctrl.word
[1] Digital only
[2] Controlword only
[0] FC
[2] Modbus RTU
[0] 2400 Baud
[1] 4800 Baud
[2] 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
[0] No function
[1] Analog Input 53
[2] Analog Input 54
[3] Pulse input 29
[100] Bus Feedback 1
[101] Bus Feedback 2
[0] Linear
[1] Square root
Danfoss A/S © 12/2015 All rights reserved.
Default
Function
[0] Digital and
Select if digital, bus, or a combination of both
ctrl.word
should control the frequency converter.
[0] FC
Select the protocol for the integrated RS485
port.
[2] 9600 Baud
Select the baud rate for the RS485 port.
[0] No function
Select which input to use as the source of the
feedback signal.
[0] Linear
Select how to calculate the feedback.
The Main Menu accesses all parameters
1.
Press [Menu] until indicator in display is placed
above Main Menu.
▲
▼
2.
Press [
] [
] to browse through the parameter
groups.
3.
Press [OK] to select a parameter group.
▲
▼
4.
Press [
] [
] to browse through the parameters in
the specific group.
5.
Press [OK] to select the parameter.
▲
▼
6.
Press [
] [
] to set/change the parameter value.