Danfoss VLT CDS 803 Quick Manual page 18

Compressor drive
Hide thumbs Also See for VLT CDS 803:
Table of Contents

Advertisement

Quick Guide
1
1
The Start-up quick guide for compressor closed-loop applications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Illustration 1.15 Closed-loop Quick Guide
16
VLT
0-01 Language
[0]
English
0-06 Grid Type
Size related
0-60 Main Menu Password
[0]
1-00 Con guration Mode
[0]
Size related
1-13 Compressor Selection
[1]
Closed loop
3-02 Minimum Reference
0
Hz
3-03 Maximum Reference
Hz
200
3-10 Preset Reference
0%
3-15 Reference 1 Source
[1]
Analog in 53
3-41 Ramp 1 Ramp Up Time
30.00
s
3-42 Ramp 1 Ramp Down Time
30.00
s
5
5-12 Terminal 27 Digital Input
[6]
Stop inverse
5-40 Function Relay 1
Alarm
5-40 Function Relay 2
Drive running
6-10 Terminal 53 Low Voltage
0.07
V
6-11 Terminal 53 High Voltage
10
V
6-14 Terminal 53 Low Ref./Feedb.
30.000
Hz
6-15 Terminal 53 High Ref./Feedb.
Hz
200.000
6-22 Terminal 54 Low Current
4.00
mA
6-23 Terminal 54 High Current
20.00
mA
6-24 Terminal 54 Low Ref./Feedb.
0.000
0
6-25 Terminal 54 High Ref./Feedb.
4999.000
20-00 Feedback 1 Source
[2]
0.00
Analog input 54
20-04 Feedback 2 Conversion
[0]
Linear
8-01 Control Site
[0]
Digital and ctrl.word
8-30 Protocol
[0]
FC
8-31 Address
1
Danfoss A/S © 12/2015 All rights reserved.
®
Compressor Drive CDS 803
MG18M202

Advertisement

Table of Contents
loading

Table of Contents