Starting The Generator; Preparations For Starting Up / Checks (Daily) For Marine Version; Preparations For Starting Up / Checks (Daily) For Vehicle Version - Fischer Panda xControl Series Manual

Table of Contents

Advertisement

Panda xControl
2.4 Starting up the generator.

2.4.1 Preparations for starting up / Checks (daily) for marine version

1. Oil level check (ideal level: 2/3 Max).
The level should be about 2/3 of the maximum level when the engine is cold.
Further, if installed, the oil level of the oil-cooled bearing must be checked before each start - see sight glass on
generator front cover!.
2. Check cooling water level.
The external expansion tank should be filled to 1/3 in a cold state. It is very important that there is sufficient
volume for expansion of the coolant.
3. Check if the raw water intake valve is open.
For safety reasons, the raw water intake valve must be shut after the generator has been switched off. It should
be re-opened before starting the generator.
4. Check raw water filter.
The raw water filter must be regularly checked and cleaned. If the raw water intake is restricted by detached
residue, this increases wear on the impeller.
5. Visual inspection
Control fixing bolts, check hose connectors for leaks, check electrical connections. Check electrical lines for
damage/chafing.
6. Switch off loads.
The generator should only be started without a load.
7. Open fuel valve, if installed.
8. Close main battery switch (switch on).

2.4.2 Preparations for starting up / Checks (daily) for vehicle version

1. Oil level check (ideal level: 2/3 Max).
The level should be about 2/3 of the maximum level when the engine is cold.
Further, if installed, the oil level of the oil-cooled bearing must be checked before each start - see sight glass on
generator front cover!.
2. Check cooling water level.
The external expansion tank should be at 1/3 in a cold state. It is very important that there is sufficient volume
available for expansion of the coolant.
3. Visual inspection
Control fixing bolts, check hose connectors for leaks, check electrical connections. Check electrical lines for
damage/chafing.
4. Switch off loads.
The generator should only be started without a load.
5. Open fuel valve, if installed.
6. Close main battery switch (switch on).
29.9.16
Chapter 2: Panda xControl - Page 13