The ELC2-PCs are 12-point (8DI + 4DO) controllers, offering various instructions and with 16k steps program memory, able to connect to all ELC series extension modules and high-speed extension modules, including digital I/O (max. 224 I/O points) and analog modules (for A/D, D/A conversion and temperature measurement). Two points of 100 kHz and two points of 10 kHz high-speed pulse outputs are included.
Specifications Item Specification Control method Stored program, cyclic scan system Batch processing method (when END I/O processing method instruction is executed) LD instructions – 0.54s, MOV instructions – Execution speed 3.4s Program language Instruction List + Ladder + SFC Program capacity 15872 steps X0~X377, octal number system,...
Page 4
Item Specification T Current value T0~T255, 256 words C0~C199, 16-bit counter, 200 words C Current value C200~C254, 32-bit counter, 55 words D0~D407, 408 words (*1) D600~D999, 400 words (*1) General D3920~D9799, 5880 words (*1) D408~D599, 192 words (*2) Word Latched D2000~D3919, 1920 words (*2) register Total...
Electrical Specifications Model ELC2-PC12NNDR ELC2-PC12NNDT Item 24 Vdc (-15 to 20%) (with reverse polarity protection on the DC input power) Power supply voltage ELC-PS01: input 100 to 240 Vac, output 24 Vdc/1A ELC-PS02: input 100 to 240Vac, output 24Vdc/2A Connector European standard removable terminal block (Pin pitch: 3.5mm) Operation...
#3: Load = 0.5A Model Name & I/O Configuration Standard functional ELC Input Output I/O Configuration Model Point Type Point Type Relay Transistor S/ S S/ S ELC2-PC12NNDR Relay (Sink or source) ELC2-PC12NNDT Transistor C OM3 + C OM3 + C OM3 - C OM3 - ...
Safety Wiring Eaton’s power supply modules ELC-PS01 orELC-PS02 are the suitable 24Vdc power supplies for ELC2-PC. We suggest you install a protective circuit at the power supply terminal to protect ELC-PS01 or ELC-PS02. See the figure below. 10 0- 24 0V...
Page 8
4. Isolation circuit: The optical coupler is used to isolate signals between the circuit inside ELC and input modules. Relay (R) output circuit wiring L ar ge r p owe r a nd E LC Re la y ou tpu t E LC Re la y ou tpu t S mal le r p owe r fr eq ue nt o n/o ff...
Page 9
The output of the transistor model is “open collector”. If Y0/Y1 is set to pulse output, the output current has to be bigger than 0.1 A to ensure normal operation of the model. 1. Diode suppression: Used when in smaller power [Figure 13a] 2.
Page 10
inside ELC2. For details of error codes (in D1004, hex coding), see “ELC System Manual: Programming”. ☼ Input indicator On/Off of input point is indicated by input indicator or monitored by ELC-HHP. When the action condition of the input point is true, this indicator will be on. If abnormality is identified, check if the indicator and input circuit are normal.
Need help?
Do you have a question about the ELC2 Series and is the answer not in the manual?
Questions and answers