Digital Alarm Communicator Transmitter (DACT). Test transmission every 24 hours shall be
enabled on each channel.
• For ULC Commercial Fire and Burglary applications the 3G2080(R) and TL2803G(R) can be
used as a passive communication module with the following security levels:
• P1 (each channel cellular or Ethernet is independent)
• P2 (cellular and Ethernet in back-up configuration, panel section [851][005] toggle option [5]
OFF).
• P3 (cellular and Ethernet in redundant configuration, panel section [851][005] toggle option [5]
ON).
• The communicator can also be used as an active communication system with the security levels
A1-A4 (each channel cellular or Ethernet independent or together in a back-up/redundant con-
figuration). For active line security systems AES128 bit encryption shall be enabled (at the
monitoring station receiver) and the supervision heartbeat rate shall be set as 90 seconds (panel
section [851][004] = 005A/90). The supervision window at the Signal Receiver Center (SRC)'s
receiver shall be programmed as maximum of 180 (00B4/180) seconds.
• For UL Residential Fire and Burglary applications the 3G2080(R) and TL2803G(R) can be
used as the primary communication channel via either cellular or Ethernet, or as a back-up in
conjunction with the DACT (30 day test transmission is required on each channel).
• For UL Commercial Burglary applications the TL2803G(R) can be used as dual signalling
line communication system (cellular and Ethernet channels used in redundant configuration),
standard line security and as encrypted line security.
• The supervision heartbeat shall be enabled (panel section [851][005] toggle option [1] (Ether-
net) and/or toggle option [2] (cellular) shall be ON), toggle option [3] (supervision type) shall
be ON and the supervision heartbeat rate shall be selected as 135 (0087/135) seconds (Option
[004] = 0087). The supervision window at the supervising station shall be maximum 200
(00C8/200) seconds. For encrypted line security systems the encryption AES128 bit shall be
enabled at the monitoring station receiver.
• For UL Commercial Burglary installations, the 3G2080(R) is listed as a primary (sole) com-
munication means (heartbeat must be enabled) or for supplementary (back-up) use in conjunc-
tion with a Plain Old Telephone Service (POTS) line dialer. When the heartbeat transmission
over the Ethernet or cellular network is enabled, using the TL2803G(R) with a compatible con-
trol unit listed for standard/encrypted line security, it can provide line security for the alarm sys-
tem over the primary line.
• The TL2803G(R) is also suitable to be used with a compatible control unit listed for dual line
security transmission when used in conjunction with a DACT or a Public Switched Data Net-
work (PSDN) transmitter, where the PSDN provides the line security and is the primary line. In
this mode, alarm signals are required to be sent simultaneously over both communication meth-
ods.