Advertisement

Product certifications
September 2019
Standards FM 3600–2011, FM 3610–2010, UL Standard 50—Eleventh edition, UL
Markings
Table B-1: Entity Parameters
Input (power) parameters
Ui - 28 Vdc
Ii - 93.3 mA
Pi - 653 mW
Ci - 5.72 nF
Li - 0
Table B-2: HART
Uo - 1.9 Vdc
Io - 32 µA
Special Conditions for Safe Use (X):
1. For use only with the Emerson Model 701PBKKF, the Computation Systems, Inc.
2. The surface resistivity of the antenna is greater than 1 GΩ. To avoid electrostatic
3. Substitution of components may impair Intrinsic Safety.
B.7

Canada

I6 Canada Intrinsically Safe (IS)
Certificate CSA 70138122
Standards CAN/CSA C22 No. 0–10, CAN/CSA C22.2 No. 94.2-15, CAN/CSA-60079-0–
Markings
Refer to
188
61010–1—3rd edition, ANSI/ISA–60079–0 (12.00.01)–2013, ANSI/ISA–
60079–11 (12.02.01)–2014
IS CL I, DIV 1, GP A, B, C, D T4 Ex ia IIC T4 Ga;
T4 (-40 °C ≤ Ta ≤ +50 °C) when installed according to Rosemount
00928-1010;
Class 1, Zone 0, AEx ia IIC T4 Ga;
Type 4X
®
Comm Parameters
MHM-89004, or the Perpetuum Ltd. IPM71008/IPM74001.
discharge buildup, it must not be rubbed or cleaned with solvents or dry cloth.
2015, CAN/CSA-60079-11–2014, CAN/CSA-C22.2 61010-1–2012
IS CL I, DIV 1, GP A, B, C, D T4;
Ex ia IIC T4 Ga;
T4 (-40 °C ≤ Ta ≤ +50 °C) when installed according to Rosemount drawing
00928-1010;
Type 4X
Table
B-1.
Output (alarm) parameters
Uo - 28 Vdc
Io -93.3 mA
Po - 653 mW
Co - 77 nF
Lo - 2 mH
Emerson.com/Rosemount
Reference Manual
00809-0100-4928
drawing