Atex; Iecex; Fm (Us & Canada) - Emerson GDU-Incus Reference Manual

Ultrasonic gas leak detector
Hide thumbs Also See for GDU-Incus:
Table of Contents

Advertisement

Certifications
December 2020
6.2

ATEX

II2 G Ex db ib IIB+H2 T4 Gb IP66/IP67
T amb -XX °C to +85 °C
XX is -55 °C when fitted with heating device.
XX is -40 °C when no heating device is fitted.
Special Conditions for Safe Use (X):
1. As flameproof joint lengths exceed the relevant minimum dimensions given in IEC
2. When temperature at the cable entry could exceed 70 °C or 80 °C at the branching
3. Minimum fastener yield stress required ≥ 450 MPa (property class A4-70).
6.3

IECEx

II 2 G Ex db ib IIB+H2 T4 IP66/IP67
T amb -XX °C to +85 °C
XX is -55 °C when fitted with heating device.
XX is -40 °C when no heating device is fitted.
IECEx ITS
10.0004X
Special Conditions for Safe Use (X):
1. As flameproof joint lengths exceed the relevant minimum dimensions given in IEC
2. When temperature at the cable entry could exceed 70 °C or 80 °C at the branching
3. Minimum fastener yield stress required ≥ 4500 MPa (property class A4-70).
6.4
FM (US & Canada)
Class I, Div. 1 Groups B, C, and D T4
Class I, Zone 1 AEx/Ex d ib IIB+H2 T4
-40 °C ≤ Ta ≤ +85 °C, Type 4X 3043275
44
60079-1:2014 Clauses 5.2 to 5.5, information on the dimensions of the flameproof
joints shall be obtained from the listed certified schedule drawings; contact the
manufacturer.
point, suitably rated cable must be selected based on the T-Class/T max.
60079-1:2014 Clauses 5.2 to 5.5, information on the dimensions of flameproof
joints shall be obtained from the listed certified schedule drawings; contact the
manufacturer.
point, suitably rated cable must be selected based on the T-Class/T max.
Reference Manual
00809-0100-3003