Testing Gateway
Redir 1

System Status Displays

[S]
ECP 67 TmPB
xx 5 ++
1234 67 TmPB Flt
5555 xx 5 ++ OK
12345678 TmPB Flt
5555555x 5 ++ OK
1234567 TmPB Flt
5555555 5 ++ OK
Bat NLd: x.xxV
Bat Ld:
Run Network Diagnostic Test
Performs a set of network diagnostics that tests the integrity
of the links between the IGSMV and the various connection
points (Redirs) to AlarmNet. Refer to Section 6: Network
Diagnostics.
ECP Mode
Flt
Displays the zone and system fault status.
OK
Press the [Space] key to go to the next field.
Press the backspace [BS] key to go to the previous field.
4204 Emulation Mode
Displays the zone and system fault status.
Press the [Space] key to go to the next field.
Press the backspace [BS] key to go to the previous field.
Two-4204 Emulation Mode
Displays the zone and system fault status.
Press the [Space] key to go to the next field.
Press the backspace [BS] key to go to the previous field.
Zone Trigger Mode
The status of the IGSMV can be viewed on the 7720P. The
status display includes:
Zone input status (1234567) - the numbers 1-7
represent the 7 mappings of the zone input, and follow
Honeywell's ADEMCO high-speed format codes:
Tm – Tamper status follows high-speed format codes
above.
P – Represents line voltage as follows:
B – Represents battery condition as follows:
Flt – Represents radio faults:
NOTE: The 7720P will not operate if the power line voltage is
removed.
Battery Voltage Display
The voltage levels of the battery connected to the
x.xxV
IGSMV can be viewed on the 7720P. The first line of the
display shows the voltage level of the battery with no load.
Section 5: Programmer Keyboard Commands
1 = New Event
5 = Normal
X = Not Enabled
+ = Power line voltage OK
– = Power line voltage bad and reported
V = Power line voltage bad, not reported (reporting
window not expired)
^ = Power voltage restored, not yet reported
+ = Battery voltage acceptable
– = Battery voltage below 5.7V ±5%
OK = Normal ; No fault
I – No network connectivity over IP and fault time
has expired
i – No network connectivity over IP and fault time
has NOT yet expired.
G = No network connectivity over GSM and fault
time has expired.
g = No network connectivity over GSM and fault
time has NOT yet expired.