Module Supervision Features; Antenna; Specifications; Mechanical - Honeywell AlarmNet IGSMV Installation And Setup Manual

Internet communication module
Table of Contents

Advertisement

IGSMV / IGSMVCN Installation and Setup Guide
 The control treats the module as 4204 Relay Module(s), so program the control
accordingly, including setting the module's proper 4204 device address
 4204 mode provides up to four zone inputs, plus two optional trigger zones, depending on
options programmed
 Two-4204 mode provides up to eight zone inputs, depending on options programmed
 Each 4204 zone can be programmed for delayed reporting and restoral reporting
 Reports are sent in ADEMCO High-Speed format
U L

Module Supervision Features

The IGSMV provides the following types of supervision and module fault detection:
 Network communication failure: In the event the AlarmNet network does not hear a
supervisory message from the module within a specified time, AlarmNet notifies the
central station of a communication failure.
 Communication path failure: In the event the module detects a communication path
failure, the control panel can be notified of a trouble condition with the module after a
specified time has elapsed ("GSM Flt Time" option, 00-99 minutes).
 Fault output: Terminal 11 can serve as a fail-safe trigger for module fault conditions.
 If used, the fault relay will trip when the following conditions occur: tamper*, power loss*,
low battery*, battery charger fault*, loss of network connectivity*, the device is not
registered and the device is remotely disabled by AlarmNet.
 * Alarm reporting for the noted condition must be enabled for it to trigger the fault relay.
 Primary power loss and low battery conditions ("Pwr Loss Rpt," "Low Bat Rpt" options).
 Cover tamper condition ("Tamper Rpt" option).

Antenna

The IGSMV comes equipped with an internal antenna. This feature provides additional
security to the installation by making the device tamper resistant.
U L/ULC
AMPS antennas, such as the 7825-OC antenna, cannot be used with this product.

Specifications

Mechanical

Dimensions: 8.4" x 8.0" x 1.5"
Weight: 2.4 lbs., with battery

Electrical

Input Power: 16.5VAC, 40VA transformer, Honeywell model No. 1361 (included)
Current Drain: 65mA average standby, 500mA peak transmit
Or
Input Power for ULC Installations: 12VDC from the control panel
Current Drain: 80mA average standby, 650mA peak transmit
1-4
4204 Mode and Two-4204 Mode has not been evaluated by UL.
External antenna has not been evaluated by UL.