IGSMV / IGSMVCN Installation and Setup Guide
PROMPTS
Supervision
18
(24 Hours)_
GSM Rollover
19
Y/N (N)_
GSM 24Hr Tst
20
Y/N (N)_
Old Alarm Time
21
10 Minutes_
IP Flt Time
22
(60 mins)_
3-14
4204/
ZONE
ENTRY
TRIG.
2-4204
OPTIONS
 30 Day
The AlarmNet network must hear at least one
 24 Hrs
supervisory message from the module during
 None
this supervision period; otherwise, AlarmNet
Additional
notifies the central station that a communica-
options for CN
tion failure has occurred. (If the supervision
only
period is changed after registration, you must
 1 Hr
re-register the module.)
 CN UL Line
Lvl 3 (3 Min)
Press the [space] key to scroll through choices.
 CN UL Line
UL: A loss of communications is treated as an
Lvl 4 (90 Sec)
Alarm condition.
CN UL
ULC: Must be set to" CN UL Line Lvl 3" for
Line Lvl 5
(75 Sec)
ULC-S304 Active Level 3 or ULC-S559 Active
Fire installations. All other commercial
applications must be set to "24 Hrs".
[Y], [N]
If enabled, all messages (including AlarmNet
network supervisory messages) are sent over
the GSM network in the event of an Internet
failure.
If disabled, all messages (except AlarmNet
network supervisory messages) are sent
automatically over the GSM network in the
event of an Internet failure.
UL/ULC: Must be set to "Y" if 24 hours is
selected in Prompt: 23: Supervision. Must be
set to "N" for ULC-S304 Active Level 3 or ULC-
S559 Active Fire installations where CN UL
Line Lvl 3 is selected.
IMPORTANT WARNING: If set to "Y", AND
Prompt 23: Supervision is set to occur less than
every 24 hours, this can result in data overage
charges on your monthly bill.
[Y], [N]
If enabled a message is sent every 24 hrs over
GSM to verify proper operation. If it fails, a
Periodic Comm Test Failure message will be
sent over Ethernet.
UL/ULC: Must be set to "Y".
 10 Min
Sets how long an undeliverable alarm is retried
 15 Min
for delivery to the central station. If the
message is not validated, it is retried until the
 30 Min
old alarm time is reached or the message is
 1 Hr
validated.
 2 Hrs
Press the [space] key to scroll through choices.
 4 Hrs
 8 Hrs
 12 Hrs
UL/ULC: Must be set to 10 minutes.
 24 Hrs
[01-99]
In the event there is a loss of contact with the
network over the Ethernet connection, enter the
time delay (in minutes) before the IGSMV
notifies the central station. IP failure will
always be sent to the central station as Primary
Communication Path Failure.
UL/ULC: Must be one (01) minute.