IGSMV / IGSMVCN Installation and Setup Guide
PROMPTS
Supervision
23
(24 Hours)_
GSM Rollover Y/N
24
(N)_
25
GSM 24Hr Tst Y/N
(N)_
26
Old Alarm Time
10 Minutes_
IP Flt Time
27
(60 mins)_
GSM Flt Time
28
(60 mins)_
3-6
ENTRY
OPTIONS
 30 Day
 24 Hrs
 None
Additional options
for CN only
 1 Hr
 CN UL Line
Lvl 3 (3 Min)
 CN UL Line
Lvl 4 (90 Sec)
CN UL Line
Lvl 5 (75 Sec)
[Y] , [N]
[Y], [N]
10 Minutes
 15 Minutes
 30 Minutes
 1 Hour
 2 Hours
 4 Hours
 8 Hours
 12 Hours
 24 Hours
[01-99]
[01-99]
DESCRIPTION
address.
2. This address must be unique from the "Device
Address" entered in Prompt 19.
The AlarmNet network must hear at least one
supervisory message from the module during this
supervision period; otherwise, AlarmNet notifies the
central station that a communication failure has
occurred. (If the supervision period is changed after
registration, you must re-register the module.)
Press the [space] key to scroll through choices.
UL: A loss of communications is treated as an Alarm
condition.
ULC: Must be set to" CN UL Line Lvl 3" for ULC-
S304 Active Level 3 or ULC-S559 Active Fire
installations. All other commercial applications must
be set to "24 Hrs".
If enabled, all messages (including AlarmNet network
supervisory messages) are sent over the GSM network
in the event of an Internet failure.
If disabled, all messages (except AlarmNet network
supervisory messages) are sent automatically over the
GSM network in the event of an Internet failure.
UL/ULC: Must be set to "Y" if 24 hours is selected in
Prompt: 23: Supervision. Must be set to "N" for ULC-
S304 Active Level 3 or ULC-S559 Active Fire
installations where CN UL Line Lvl 3 is selected.
IMPORTANT WARNING: If set to "Y", AND Prompt
23: Supervision is set to occur less than every 24
hours, this can result in data overage charges on your
monthly bill.
If enabled a message is sent every 24 hrs over GSM to
verify proper operation. If it fails, a Periodic Comm
Test Failure message will be sent over Ethernet.
UL/ULC: Must be set to "Y".
Sets how long an undeliverable alarm is retried for
delivery to the central station. If the message is not
validated, it is retried until the old alarm time is
reached or the message is validated.
Press the [space] key to scroll through choices.
UL/ULC: Must be 10 minutes.
In the event there is a loss of contact with the network
over the Ethernet connection, enter the time delay (in
minutes) before the IGSMV notifies the central
station. IP failure will always be sent to the central
station as Primary Communication Path Failure.
UL/ULC: Must be one (01) minute.
In the event the module detects a communication path
failure, enter the time delay (in minutes) before the
IGSMV notifies the central station. A GSM failure
will always be sent to the central station as Secondary
Communication Path Failure.
UL/ULC: Must be one (01) minute.