Power Connections And Options; Powering The Communication Module - Honeywell AlarmNet IGSMV Installation And Setup Manual

Internet communication module
Table of Contents

Advertisement

IGSMV / IGSMVCN Installation and Setup Guide

Power Connections and Options

Powering the Communication Module

There are three ways to power the communications module (see Figure 2-8 below):
Standard Installation – The communications module is powered by the supplied AC plug-
in transformer.
ULC Commercial Fire and Burglary Compliant Installation – The communications
module must be powered by the control panel.
Shared Transformer Installation – In this installation the supplied AC plug-in
transformer may be used to power both the communications module and the control panel
under the following conditions:
 You must use the Honeywell 1361 Transformer.
 This configuration ONLY applies to the VISTA-10P, VISTA-15P, VISTA-20P control
panels when used with the GSMV or IGSMV Communications Module.
 DO NOT use this configuration with any other control panel.
 DO NOT use this configuration if using two-way voice.
 This configuration has not been evaluated by UL.
For all installations the control panel ground (GND) must be connected to TB1-4 GND on the
communications module. In addition, if using ECP communication, you must connect the
+12VDC AUX voltage output on the control panel (9.6V-13.8V typical) to TB1-3 on the
communications module.
Standard
Installation
ULC Commercial
Fire and Burglary
Compliant
Installation
2-8
TRANSFORMER
12V AUX
GND
CONTROL PANEL
+12 V AUX
GND
DATA OUT
DATA IN
CONTROL PANEL
NOTE: DO NOT CONNECT THE COMMUNICATION
MODULE BACKUP BATTERY OR TRANSFORMER
FOR COMMERCIAL FIRE & BURGLARY INSTALLATIONS.
TB1
1
AC INPUT 1
AC INPUT 2
2
ECP (+) VOLTAGE INPUT
3
GND
4
COMMUNICATIONS
MODULE
TB1
AC INPUT 1
1
NO CONNECTION
AC INPUT 2
NO CONNECTION
2
RED
ECP (+) VOLTAGE INPUT
3
BLK
GND
4
YEL
5
ECP DATA IN
GRN
6
ECP DATA OUT
COMMUNICATION MODULE
BATTERY
J1
J1
NO CONNECTION
comm_mod-001-V1