Honeywell AlarmNet IGSMV Installation And Setup Manual page 38

Internet communication module
Table of Contents

Advertisement

IGSMV / IGSMVCN Installation and Setup Guide
PROMPTS
37
Invert Zn2 Y/N
(N)_
Restore Zn2 Y/N
38
(Y)_
Delay Zn2 (secs)
39
(00)_
Rpt Zn2 ONLY if
40
Armed (N)_
If Lynx Panic is enabled, then skip to Prompt 45: "Rpt Zn3 ONLY if Armed."
Zn3 Trigger Type
41
(V+)_
42
Invert Zn3 Y/N
(N)_
Restore Zn3 Y/N
43
(Y)_
Delay Zn3 (secs)
44
(00)
Rpt Zn3 ONLY if
45
Armed (N)_
Zn4 Trigger Type
46
(V+)_
47
Invert Zn4 Y/N
(N)_
48
Restore Zn4 Y/N
(Y)_
Delay Zn4 (secs)
49
(00)
3-18
4204/
ZONE
ENTRY
TRIG.
2-4204
OPTIONS
[Y], [N]
Inverts the alarm and normal states of the
zone 2 trigger; otherwise uses normal input
signal.
[Y], [N]
Enables restore reporting for zone 2.
UL/ULC: Must be set to "Y."
[01-15]
Defines the reporting delay in seconds for
zone 2.
[00] = no delay
UL/ULC: Must be set to "00."
[Y], [N]
Reports alarms on zone 2 ONLY if the
conditional zone (zone 7 in zone trigger mode;
zone 4 in 4204 mode; zone 8 in 2-4204 mode)
is triggered (armed).
If [N], always reports alarms on zone 2.
 (V+)
Selects the triggering method for this zone
 (V–)
input.
 (EOLR)
Press the [space] key to scroll through
choices.
UL: V+ must be set as inverted and V– as
non-inverted.
[Y], [N]
Inverts the alarm and normal states of the
zone 3 trigger; otherwise uses normal input
signal.
[Y], [N]
Enables restore reporting for zone 3.
UL/ULC: Must be set to "Y."
[01-15]
Defines the reporting delay in seconds for
zone 3.
[00] = no delay
UL/ULC: Must be set to "00."
[Y], [N]
Reports alarms on zone 3 ONLY if the
conditional zone (zone 7 in zone trigger mode;
zone 4 in 4204 mode; zone 8 in 2-4204 mode)
is triggered (armed).
If [N], always reports alarms on zone 3.
4204 mode: If any zone is programmed to
"Report Only if Armed," skip to Prompt 56:
"Enable Zn6."
 (V+)
Selects the triggering method for this zone
 (V–)
input.
 (EOLR)
Press the [space] key to scroll through
choices.
UL: V+ must be set as inverted and V– as
non-inverted.
[Y], [N]
Inverts the alarm and normal states of the
zone 4 trigger; otherwise uses normal input
signal.
[Y], [N]
Enables restore reporting for zone 4.
UL/ULC: Must be set to "Y."
[01-15]
Defines the reporting delay in seconds for
zone 4.
[00] = no delay
UL/ULC: Must be set to "00."