2.5 External Environment Requirements

Issue 02 (2020-01-15)
pre-fab. module ground point. When a ground grid is pre-buried, the ground lug
must be long enough to connect to a ground point on the pre-fab. module.
Ground cable method: Use a 95 mm
the cable to the pre-buried ground grid, and connect the other end to the pre-fab.
module ground point. When a ground cable is used, the ground cable must be routed
through a plastic-coated metal hose.
The screw reserved at a ground point is an M12 screw.
A pre-fab. module can be grounded in the TN-S or TN-C-S mode.
Temperature: –20° C to +55° C
Relative humidity: 5%–95% RH
Solar radiation: ≤ 1120 W/m