ABB SF6 LTB 245E1 BLG 1002A Product Manual page 34

Operatin mechanism 3-pole operation
Table of Contents

Advertisement

Delivery
3.3.3 Operating mechanism
3.3.4 Circuit-breakers
3.3.5 Spare parts
8
The operating mechanism should be unpacked on arrival. If it is not kept in an
approved store, the heating element must be connected and permanently switched
on to prevent the control equipment from corrosion or damage due to freezing.
The circuit-breakers should be stored in their original cases where they are properly
protected from damage. The units shall not stand in water. The circuit-breakers can
be stored outdoors. If this happens they should be protected by at least a tarpaulin.
The tarpaulin must not be so tight that air circulation to zinc coated surfaces is
prevented. Any condense should easily drip off.
The lowest permitted ambient temperature for storage is -30˚C.
Spare parts shall be kept indoors in an approved store and in their original packing.
This is especially important for rubber components (seals etc.), which must also be
protected from sunlight to avoid drying. Gaskets have a limited storage life, so avoid
storing them. Frames can be stored outdoors.
Assembly Instructions
1HSB435410-2 enrev1