Drive Unit - ABB SF6 LTB 245E1 BLG 1002A Product Manual

Operatin mechanism 3-pole operation
Table of Contents

Advertisement

Maintenance

4.7 Drive unit

Item
1
Drive unit
4.7.1 Switch Hand-Motor
16
Check and clean the shafts in the catch gear and the worm gears in the drive
unit.
Lubricate these with Grease "M" at intervals of 3-6 years or 2,000 operations.
Measure the motor current at the end of the spring charging procedure at
intervals of 15 years or 5,000 operations. See the relevant Assembly
Instructions for the circuit-breaker, chapter Operating values.
The motor should be capable of charging the springs at 85% of its nominal voltage
(IEC).
B20011
Check that the signal for voltage failure functions. If not, replace the switch.
Operating Mechanism Maintenance
1
Figure 4-7. Drive unit
1HSB515409-100 en rev2