Operating Mechanism Maintenance

4.8 Catch gear

Item
1
Catch gear
Item
1
Auxiliary catch
2
Magnet arm
1HSB515409-100 en rev2
The operating mechanism is fitted as standard with one closing coil and two
opening coils, but can, on request, be equipped with double coils on the closing side.
B20012
Check that the voltage to the coils does not fall below the minimum voltage,
see the delivery document for the operating mechanism.
Check the play between the magnet arm and the auxiliary catch . The play must
be at least 1 mm. If the plays are outside the specified dimensions, replace the
entire catch gear.
B20013
Closing catch gear
1
Opening catch gear
Figure 4-8. Catch gear
1
2
Figure 4-9. Checking the clearance.
Maintenance
1 mm
17