Inspecting The Bolted Joints, Etc - ABB SF6 LTB 245E1 BLG 1002A Product Manual

Operatin mechanism 3-pole operation
Table of Contents

Advertisement

Assembly Instructions

4.10 Inspecting the bolted joints, etc.

1HSB435410-2 enrev1
Check using a 6 mm diameter rod, that the arm's alignment check hole is
aligned with the predrilled hole in the mechanism housing.
Check that all bolted joints are tightened to the correct torque in accordance
with the table below.
Bolted joint
Frame
Foundation
Operating mechanism
Protective tube
Circuit-breaker pole
Pull-rod
Density monitor
Bottom cover
Plates
Cover
Tightening torque (Nm)
430
300-350 or 500-550
79
79
300
300
10
22,5
22,5
9
Assembly