Operating and Maintenance Instructions
To be inspected
6.
Main current circuit
•
Resistance check.
7a.
Contact system
•
Opening position
7b.
Operating
characteristics
•
Opening time
•
Closing time
•
Close-Open time
•
Phase discrepancy
•
Auxiliary switches
•
Contact travel
•
Contact damping.
1HSB435409-100 en1
Inspection interval
15 years or 5,000 mech CLOSE/
OPEN operations.
Circuit-breakers only operating
<100 CLOSE/OPEN
operations/year after 6-8 years or
2500 mech CLOSE/OPEN
operations.
15 years or 5,000 mech. CLOSE/
OPEN operations.
15 years or 5,000 mech. CLOSE/
OPEN operations.
Inspection intervals
Measures / Instructions /
Check resistance of circuit-breaker.
Resistance bridge, test current min.
200 A DC.
Resistance value as specified in
applicable Assembly instructions for the
circuit-breaker in question.
Higher values allowed for frequent
operation with small currents (≤400Α).
Calculation of permissible resistance:
1.65
Rn
In
R
=
------ -
---- -
2
I
R =
Permissible increase in
resistance
R
= Max. resistance as specified
n
in operating values
I
=
Rated current as specified on
n
rating plate
I =
Current for which max.
resistance is calculated.
'
Inspection of reference holes in outer
lever and mechanism housing.
See applicable Assembly instructions
for the circuit-breaker in question.
Measurement with electronic timer.
Nominal operating voltage.
For times, see the applicable Assembly
instructions for the circuit-breaker.
Max phase discrepancy between
phases:
at closing 4 ms; at opening 3 ms.
max discrepancy between breaks in the
same phase:
at closing 3 ms; At opening 2 ms.
See Manual 1HSB515409-100 for BLG
1002A or 1HSB535409-100 for BLK
222.