ABB SF6 LTB 245E1 BLG 1002A Product Manual page 84

Operatin mechanism 3-pole operation
Table of Contents

Advertisement

Operating and Maintenance Instructions
To be inspected
6.
Main current circuit
Resistance check.
7a.
Contact system
Opening position
7b.
Operating
characteristics
Opening time
Closing time
Close-Open time
Phase discrepancy
Auxiliary switches
Contact travel
Contact damping.
1HSB435409-100 en1
Inspection interval
15 years or 5,000 mech CLOSE/
OPEN operations.
Circuit-breakers only operating
<100 CLOSE/OPEN
operations/year after 6-8 years or
2500 mech CLOSE/OPEN
operations.
15 years or 5,000 mech. CLOSE/
OPEN operations.
15 years or 5,000 mech. CLOSE/
OPEN operations.
Inspection intervals
Measures / Instructions /
Check resistance of circuit-breaker.
Resistance bridge, test current min.
200 A DC.
Resistance value as specified in
applicable Assembly instructions for the
circuit-breaker in question.
Higher values allowed for frequent
operation with small currents (≤400Α).
Calculation of permissible resistance:
1.65
Rn
In
R
=
------ -
---- -
2
I
R =
Permissible increase in
resistance
R
= Max. resistance as specified
n
in operating values
I
=
Rated current as specified on
n
rating plate
I =
Current for which max.
resistance is calculated.
'
Inspection of reference holes in outer
lever and mechanism housing.
See applicable Assembly instructions
for the circuit-breaker in question.
Measurement with electronic timer.
Nominal operating voltage.
For times, see the applicable Assembly
instructions for the circuit-breaker.
Max phase discrepancy between
phases:
at closing 4 ms; at opening 3 ms.
max discrepancy between breaks in the
same phase:
at closing 3 ms; At opening 2 ms.
See Manual 1HSB515409-100 for BLG
1002A or 1HSB535409-100 for BLK
222.