Toshiba G9000 Series Installation And Operation Manual page 59

Scib energy storage system
Hide thumbs Also See for G9000 Series:
Table of Contents

Advertisement

Simulated Cell Over Voltage Warning and Contactor Open Test
Binary: 10100000101
Decimal: 1285
Register 40014 (System Warning Status) – Simulated Cell Over Voltage Warning and
Contactor Open Test
Bit Number
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Simulated Cell Under Voltage Warning and Contactor Open Test
Binary: 100100001001
Decimal: 2313
Register 40014 (System Warning Status) – Simulated Cell Under Voltage Warning and
Contactor Open Test
Bit Number
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002
Value
Status Description
1
Left String Contactor Open
0
Left String Over Cell Temp Warning
1
Left String Over Cell Voltage Warning
0
Left String Under Cell Voltage Warning
0
N/A
0
Reserved
0
Reserved
0
Reserved
1
Right String Contactor Open
0
Right String Over Cell Temp Warning
1
Right String Over Cell Voltage Warning
0
Right String Under Cell Voltage Warning
0
N/A
Value
Status Description
1
Left String Contactor Open
0
Left String Over Cell Temp Warning
0
Left String Over Cell Voltage Warning
1
Left String Under Cell Voltage Warning
0
N/A
0
Reserved
0
Reserved
0
Reserved
1
Right String Contactor Open
0
Right String Over Cell Temp Warning
0
Right String Over Cell Voltage Warning
1
Right String Under Cell Voltage Warning
0
N/A
51

Advertisement

Table of Contents
loading

Table of Contents