7

Installation

7.1

Installation Precautions

Keep the SPECIFIED CLEARANCE around the SCiB ESS.
Inadequate space around the ESS makes it difficult to perform maintenance/inspections,
lead to insufficient ventilation, and/or will cause malfunctions.
See 7.2 Installation Procedure
DO NOT tilt the SCiB ESS cabinet(s) more than 10° from upright position.
Tilting the SCiB ESS cabinet(s) more than 10° may cause crushing, trapping or other personal
injuries.
Install anchor bolts to secure the SCiB ESS to the installation floor.
The SCiB ESS may fall during an earthquake if the anchor bolts are not installed and secured.
DO NOT transport, move, store, or place the SCiB ESS on its side.
Forces due to heavy components inside may damage the cabinet(s).
DO NOT allow the SCiB ESS to suffer shock or impact when unpacking.
Tools used to remove packaging materials may cause damage to the cabinet(s).
DO NOT push or pull on the sides of the SCiB ESS packaging to move it. ONLY use a
forklift to transport the SCiB ESS.
Pushing/pulling on the sides of the unit to move it may result in damage to the SCiB ESS.
See Section 4.
Only factory authorized personnel should relocate, modify, or replace parts in the
SCiB ESS after initial installation.
Electrical shock, injury or UPS/ESS failure may occur if non-authorized technicians attempt
to modify or relocate the SCiB ESS.
Please contact Toshiba Customer Support Center if you plan to move or make modifications
to the UPS
Install the UPS system in a controlled environment.
Improper storage and installation environment may deteriorate insulation, shorten component
life and cause malfunctions.
See Section 6.2 Storage Environment
G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002
WARNING
CAUTION