Over temp. (fault protected by BMU)
Max. cell voltage (warning)
Min. cell voltage (warning)
Over temp. (warning)
Cell balancing function
LED status
7-seg. LED for warning
7-seg. LED for cabinet fault
7-seg. LED for left string fault
7-seg. LED for right string fault
Firmware Version
Name
Left string voltage
Right string voltage
Left string charge current
Left string discharge current 40035
Right string charge current
Right string discharge cur-
rent
Left string min. cell temp. /
module No.
Left string max. cell temp. /
module No.
Right string min. cell temp. /
module No.
G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002
40021
40022
40023
40024
40025
40026
40027
40028
40029
40030
40031
String Information Holding Registers
Register
Number
15
14
13
40032
Left string voltage value is indicated by 0.1V/LSB (6553.5V to 0V)
40033
Right string voltage value is indicated by 0.1V/LSB (6553.5V to 0V)
Left string current value in the charge direction is indicated by 0.01A/LSB
40034
(655.35A to 0A)
Left string current value in the discharge direction is indicated by 0.01A/LSB
(655.35A to 0A)
Right string current value in the charge direction is indicated by 0.01A/LSB
40036
(655.35A to 0A)
Right string current value in the discharge direction is indicated by 0.01A/LSB
40037
(655.35A to 0A)
Left string min. temp. value / of all cells
40038
indicated by 1°C/LSB. Usage range
-40°C to 125°C
Left string max. temp. value / of all cells
40039
indicated by 1°C/LSB. Usage range
-40°C to 125°C
Right string min. temp. value / of all
40040
cells indicated by 1°C/LSB. Usage
range -40°C to 125°C
Fault temp. indicated by 1°C/LSB (75°C)
Max. cell voltage indicated by 1mV/LSB (2.7V)
Min. cell voltage indicated by 1mV/LSB (1.5V)
Fault temp. indicated by 1°C/LSB (55°C)
Reserved
System warning status (65535-0)
Cabinet fault status (65535-0)
Left string fault status (65535-0)
Right string fault status (65535-0)
Version(12 bit)
Bit Number
12
11
10
9
8
Reserved
b5 b4 b3 b2 b1 b0
Revision (4 bit)
7
6
5
4
Module No. containing the minimum
cell temperature value in Left string.
Usage range: module No. 1 to 28.
Module No. containing the maximum
cell voltage value in Left string. Usage
range: module No. 1 to 28.
Module No. containing the minimum
cell temperature value in Right string.
Usage range: module No. 1 to 28.
b1 b0
3
2
1
0
41