Register Details - Toshiba G9000 Series Installation And Operation Manual

Scib energy storage system
Hide thumbs Also See for G9000 Series:
Table of Contents

Advertisement

Right string max. cell temp. /
module No.
Left & Right string average
cell temp.
Left string min. cell voltage
Left string max. cell voltage 40044
Left string min./max. cell
voltage module No.
Right string min. cell voltage 40046
Right string max. cell voltage 40047
Right string min./max. cell
voltage module No.
Left String SOC (%)
Left String SOH (%)
Right String SOC (%)
Right String SOH (%)
Left String SOC(%)/ Avg Cell
Temp
Right String SOC(%)/ Avg
Cell Temp

Register Details

Registers with additional information beyond what is shown in the above tables are detailed below.
40010 – Host Status
Bits 0-2: cabinet ID
Up to eight cabinets with ID from 0x000 to 0x111 determined by DIP switch setting
Bits 3-5 : Host Status
Abnormal (b3): 1 – System is in fault or short start-up period. Both contactors are open.
Ready (b4):
Service (b5):
Bits 6-7: contactor status
0 – Open; 1 – Closed
42
Right string max. temp. value / of all
40041
cells indicated by 1°C/LSB. Usage
range -40°C to 125°C
Left string average temp. value of all
40042
cells indicated by 1°C/LSB. Usage
range -40°C to 125°C
40043
Left string min. voltage value of all cells indicated by 1mV/LSB
Left string max. voltage value of all cells indicated by 1mV/LSB
Module No. containing the minimum
40045
cell voltage value in Left string. Usage
range: module No. 1 to 28.
Right string min. voltage value of all cells indicated by 1mV/LSB
Right string max. voltage value of all cells indicated by 1mV/LSB
Module No. containing the minimum
40048
cell voltage value in Right string. Us-
age range: module No. 1 to 28.
40049
40050
40051
40052
40053
40054
1 – System has no fault. One or more contactors is open.
1 – System has not fault. Both contactors are closed.
G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002
Module No. containing the maximum
cell voltage value in Right string. Us-
age range: module No. 1 to 28.
Right string average temp. value of all
cells in indicated by 1°C/LSB. Usage
range -40°C to 125°C
Module No. containing the maximum
cell voltage value in Left string. Usage
range: module No. 1 to 28.
Module No. containing the maximum
cell voltage value in Right string. Us-
age range: module No. 1 to 28.