4. The SCiB ESS ships with individual battery modules disconnected. Strings should be connected using jumper wires
shipped with the cabinets. See Figure 7.8. for connection details. Note: voltage exists at battery terminals. Proper
PPE should be worn during this step. Use ONLY the screws provided with the jumpers to connect the wire to
the battery terminals. Incorrect screw size can lead to loose connection and possible damage to the battery
terminal. Correct screw size for jumpers is M6x12mm. Correct screw size for top bus bar is M6x16mm.
5. Multiple color-coded ethernet communication connections must be made within the SCiB ESS cabinet(s). They are
listed below and shown in Figure 7.9 as well as the enlarged diagram below.
a. RJ-CMU101 connected to Battery 101 communication input.
b. RJ-CMU201 connected to Battery 201 communication input.
c. RJFT-1 and RJFT-2 connected to the corresponding RJFT-1 and RJFT-2 on the fuse trays.
Each fuse tray contains a micro-switch that will trip the battery breaker if removed.
This is a safety measure that must be kept in mind when manipulating the fuse
trays. Micro-switch is located behind the right side screw of the tray. When the
screw is tightened it closes the micro-switch making a closed connection. As soon
as the screw is loosened, the micro-switch will cause a fault and interrupt the bat-
tery connection.
7.6

Customer Supplied Equipment

1. CAT 5E SSTP Cables – Cables for cabinet to cabinet communication
2. Control Wiring – 480VAC control power should be supplied from customer's distribution panel which is supplied form
the output of the UPS. (2-wire, 480VAC). See Figure Figure 7.7.
Control Wiring Recommendations
Wire Type
Solid
Stranded
Stranded Tin-Bonded
26
RJ-CTRL
RJ-CMU101
RJ-PWR1
RJ-FT1
RJ-FT2
CAUTION
Wire Size
#12 – #14
#12 – #14 (19 Strand or Less)
#12 – #14 (19 Strand or Less)
Recommended Breaker Size
Trip Rating
10A, 2-Pole
G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002
RJ-FT1
RJ-FT2
RJ-CMU201
RJ-SVC1
RJ-SVC2
RJ-PWR2
Voltage
600VAC
Voltage
600VAC
600VAC
600VAC