Technician Settings P11 to P15

P11 – Window contact delay time
Range: 0...999 seconds.
Default: 600 seconds.
P12 – Door switch (terminals T1,0) polarity
"01" -
Normally open
"00" -
Normally closed
P13 – Door switch delay time
Range: 0...999 seconds.
Default: 180 seconds.
P14 – Enable/Disable Auto change over mode
"00" -
Disable Auto change over mode
"01" -
Enable Auto change over mode
P15 – Motion sensor logic (PIR)
"00" -
Thermostat turns off when unoccupied and back on
when re-occupied.
"01" -
Thermostat turns off when unoccupied and remains
off when re-occupied.
"02" -
Thermostat uses economy setpoints when
unoccupied.