Wiring and DIP Switch configurations 14 to 15 – AC systems
with Humidifier for humidification
Config. 14:
Outputs
1 Speed fan, Humidifier
Heat element 2
11
Economizer
12
(option – SW1.6 ON)
Fan (1 speed)
13
Compressor 2
14
Compressor 1
15
16
AO1
Humidifier
AO2
SW3
SW1
(1)
SW3.1, SW3.2 – Fan speeds:
(2)
SW3.4 – HP (Heat pump):
HC (not heat pump):
(3)
SW3.5 – Compressor delay:
(4)
SW1.3 – Dehumidification:
(5)
SW1.6 – Terminal 12 operation:
See drawing for DIP switch and jumper locations (page 24).
Fan on/off: 110-230VAC, 2.5A max., Humidifier: 0-10VDC, 0.5mA Not isolated
Control - Heat elements, Heat pump, Compressors, Economizer: 110-230VAC, 0.3A max.
ComfortVu™ BACnet Thermostat Model Standard TB-HM (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide
HC12
1 Speed fan, Humidifier,
Dehumidification
Heat element
(2)
(2nd stage heat)
Economizer
(5)
(option – SW1.6 ON)
Fan (1 speed)
Heat Pump
Compressor
(3)
X
X
2 speeds (Low and High):
3 speeds (Low, Med., and High):
ON = Heat pump active in cool, OFF = Heat pump active in heat
ON = Electrical heater, OFF = Oil/Gas heater (no fan)
ON = Disable, OFF = Enable
ON = Use dehumidifier, OFF = Use reheat for dehumidification
ON = Economizer
OFF = Fan Medium (3 speeds) / Terminal not in use (2 speeds)
Important: Economizer will not work in 3 fan speeds configuration.