Wiring And Dip Switch Configurations 45 To 47 - Fc Systems - 4-Pipe - Carrier ComfortVu TBPL-24-H Installation And Operation Manual

Bacnet thermostat standard tb-hm line voltage
Hide thumbs Also See for ComfortVu TBPL-24-H:
Table of Contents

Advertisement

Wiring and DIP Switch configurations 45 to 47 – FC systems - 4-pipe
with Dehumidifier
Config. 45:
Outputs
4-Pipe, 1/2/3 Speeds
(1)
fan
, Dehumidifier
Fan high
11
Fan medium
12
(or Economizer
Fan low
13
Heat valve
14
Cool valve
15
16
AO1
Dehumidifier
AO2
SW3
SW1
(1)
SW3.1, SW3.2 – Fan speeds:
(2)
SW3.4 – 2nd heating stage:
(3)
SW3.5 – Chilled beam option:
(4)
SW1.3 = Dehumidification:
(5)
SW1.6–Terminal 12 operation:
See drawing for DIP switch and jumper locations (page 24).
Fan on/off: 110-230VAC, 2.5A max., PID valves, Dehumidifier: 0-10VDC, 0.5mA Not isolated
Control - Heat elements, Cool/Heat valves, Economizer: 110-230VAC, 0.3A max.
ComfortVu™ BACnet Thermostat Model Standard TB-HM (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide
Config. 46:
4-Pipe, 1/2/3 Speeds
fan
(1)
, Cool valve PID,
Dehumidifier
Fan high
Fan medium
)
(or Economizer
(5)
Heat valve
(3)
X
X
Cool valve PID
Dehumidifier
1 speed (Low):
2 speeds(Low and High):
3 speeds(Low, Medium, and High):
ON = Enable, OFF = Disable
ON = Enable chilled beam (fan will not run with cooling)
ON – Use dehumidifier, OFF – Use reheat for dehumidification
ON = Economizer
OFF = Fan Medium (3 speeds) / Terminal not in use (1/2 speeds/VFS)
Important: Economizer will not work in 3 fan speeds configuration.
4-Pipe, 1/2/3 Speeds
fan
)
(or Economizer
(5)
Fan low
X
X
Heat valve PID
(3)
41
Config. 47:
(1)
, Heat valve PID,
Dehumidifier
Fan high
Fan medium
)
(5)
Fan low
Cool valve
(3)
X
X
Dehumidifier
SW3.1 = ON, SW3.2 = OFF
SW3.1 = OFF, SW3.2 = ON
SW3.1 = OFF, SW3.2 = OFF
All rights reserved