Specifications - Carrier ComfortVu TBPL-24-H Installation And Operation Manual

Bacnet thermostat standard tb-hm line voltage
Hide thumbs Also See for ComfortVu TBPL-24-H:
Table of Contents

Advertisement

Specifications

Sensing element:
Temperature
Humidity
Motion Sensing:
Sensor Type
Distance
Detection range
Movement speed
Detection object
Power
Communication
Inputs
Outputs
Environmental operating range
Mounting
Weight
ComfortVu™ BACnet Thermostat Model Standard TB-HM (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide
Range
41° F to 95° F (5° C to 35° C)
10% to 90 %
PIR, quad, omnidirectional
16.4 feet (5m)
(HxV) 90° x 30°
2.62 to 3.94 ft/s (0.8 to 1.2 m/s)
15.75 x 9.84 in. (400 x 250 mm)
85 to 240 Vac, 50-60Hz, 1.5 VA
NOTE Devices connected to outputs, such as a fan, will increase VA
requirements.
BACnet MS/TP with baud rates up to 76.8 kbps (default baud rate is 38.4
kbps), detected and set automatically by the BACnet Thermostat. Max 127
devices.
T1, 0 – Normally open or normally closed dry contract, or
0-10 Vdc analog input, or
50 kOhm thermistor @ 25°C
A, B - Communication +/- (RS485)
IN1, 0 - Normally open or Normally closed dry contract, or
0-10 Vdc analog input, or
50 kOhm thermistor @ 25°C
C, R - Power: 24 Vac
11, 12, 13 – Digital outputs, 3A max.
14 – Digital outputs 0.3A max.
15 and 16 – Depends on application.
Digital output 0.3A max., or
Analog output 0-10 Vdc, 5 mA max., not isolated
50° to 122° F (10° to 50° C), 10 to 90% relative humidity, non-condensing
Wall mount on a standard 4" x 2" electrical box using provided 6/32 x 1/2" mounting
screws
4.8 oz (0.14 kg)
Accuracy
±1.0° F (0.5° C)
±3.0% typical
2
All rights reserved