DIP switch and jumper configurations

SW4.1 – Without valves control in FC config.
Enable = OFF (Open)
Disable = ON (Closed)
SW4.2 – Enable/Disable PIR detector
OFF - Enable PIR detector
ON - Disable PIR detector
SW4.3 – Not used
Always OFF
ComfortVu™ BACnet Thermostat Model Standard TB-HM (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide
SW4.4 - End of line resistor (120Ω)
OFF = Not end of line
ON = End of line
SW1.1 through SW1.6, and SW3.1 through SW3.8
See Wiring and DIP switch/jumper settings (page 28).
24