Port: Simple Switching; Port: Advanced Switching (Batchmode) - Gude Expert Power Control 8032-1 Manual

Table of Contents

Advertisement

Operating
Credit: 130.50 Eur
Sensor 1: N.C.
Sensor 2: N.C.
Sensor 3: N.C.
Temp. 4: 25.8 C

2.4.1.1.2 Port: Simple Switching

Format
%port
[on, off, toggle] [portnumber]
Examples:
Switch off Output Port 2, Mastercode 2222
%port
off 2
m2222
Toggle Output Port 8, Portcode 1238
%port
toggle 8
p1238
Reset Output Port 6, Portcode 0123
%port
reset
6
p0123
Switch on Output Port 1, without Portcode
%port
on 1
Answer (example):
Device name: epc007
Port switch: Port 1 off -> on
Account Credit: Credit: 130.50 Eur

2.4.1.1.3 Port: Advanced Switching (Batchmode)

Format
%port batchmode
[batch-sequence-number]
'11' .. '19' off, wait [t1 .. t9]s, on
'21' .. '29' on, wait [t1 .. t9]s, off
'31' .. '39' toggle, wait [t1 .. t9]s, toggle
Note: Sequence numbers are identical to the DTMF codes for voice calls.
Expert Power Control 8032
{Portcode/Mastercode}
[portnumber] [batch-sequence-number]
{Portcode/Mastercode}
26
© 2020 GUDE Systems GmbH