C
Table C-1 Associations between UIM02C dry contacts and alarms
Silk
Port Type
Screen
Dry contact
DIN1
input ports
DIN2
DIN3
DIN4
DIN5
DIN6
Dry contact
ALM1
output ports
The default
setting (closed:
normal; open:
alarm) can be
ALM2
modified.
ALM3
ALM4
ALM5
ALM6
Issue 07 (2019-11-15)
Associations Between Alarms and Dry
Name
-
-
-
-
-
-
Urgent alarm
Not urgent alarm
System incident
AC
Rectifier incident
Battery incident
Copyright © Huawei Technologies Co., Ltd.
C Associations Between Alarms and Dry Contacts on the
Contacts on the UIM
Category
Associated Alarm
Dry contact input 1 (open: normal;
-
closed: alarm)
-
Dry contact input 2 (open: normal;
closed: alarm)
Dry contact input 3 (open: normal;
-
closed: alarm)
-
Dry contact input 4 (open: normal;
closed: alarm)
-
Heater Fault (closed: normal; open:
alarm)
-
Dry contact input 6 (open: normal;
closed: alarm)
System
BLVD Warning/BLVD
incident
Disconnected/Batt. Fuse Break/SMU
Fault/Batt Test Negative/Rectifier
Fault/DC Undervolt./DC Ultra
Undervolt.
System
Insuff. Rdnt. Rects./Rectifier Fault/Fan
incident
Fault/AC Ph. Failure
AC main
AC Ph. Failure/AC Failure/Long Mains
Failure
Ret. Vent TS Fault/Fan Fault
-
Rectifier Fault
-
Batt. Fuse Break/Batt Test Negative
UIM
59