UPS2000-(1 kVA-3 kVA)
V200R001
User Manual
Issue
03
Date
2015-06-08
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the UPS2000-A-1KTTS and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Huawei UPS2000-A-1KTTS

  • Page 1 UPS2000-(1 kVA-3 kVA) V200R001 User Manual Issue Date 2015-06-08 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 4: Change History

    This is the third release. Updated the alarm handling Issue 02 (2014-12-01) This is the second release. Added chapter 7 Routine Maintenance. Issue 01 (2014-10-27) This is the first release. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 5: Table Of Contents

    4.4 Buttons ..................................27 4.5 Setting Parameters ..............................29 4.6 Operating Modes ................................ 33 4.7 Alarm Handling ................................34 4.8 Alarm Indication ................................. 42 5 Troubleshooting .......................... 43 Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 6 7.2.4 Yearly Maintenance ..............................50 8 Specifications ..........................51 8.1 Tower-mounted UPS Specifications ........................... 51 8.2 Rack-mounted UPS specifications ..........................54 A Acronyms and Abbreviations ....................58 Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 7: Precautions

    Keep the UPS away from the following environments:  Places where the temperature and humidity are beyond the range of 0–40° C and 0%–95% RH respectively Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 8: Installation

     To completely disconnect the UPS, shut down the UPS and then unplug the power cable.  Prevent liquid or any other foreign objects entering the UPS. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 9: Servicing, Maintenance, And Troubleshooting

    Electric shock risk. The battery circuit is not disconnected from the input voltage. It is possible to have a dangerous voltage between the battery terminal and the ground cable. Therefore, ensure that no voltage exists before touching the UPS interior. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 10: Overview

    UPS2000-A-3KTTL 3 K-long backup time model-tower mounted-IEC UPS2000-G-3KRTS 3 K-standard model-rack mounted-IEC UPS2000-G-3KRTL 3 K-long backup time model-rack mounted-IEC Figure 2-1 shows the UPS model number. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 11: Product Structure

    1–3 kVA tower-mounted standard UPS and long UPS respectively. Figure 2-4 Figure 2-5 shows the rear view of a 3 kVA rack-mounted UPS. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 12: Rear Views Of Tower-Mounted Upss

    (1) Mains input socket (1 kVA/2 kVA: C13; (2) Input circuit breaker 3 kVA: C19) (3) Universal serial bus (USB) port (security (4) RS232 port protection mechanism supported) Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 13: Rear Views Of Rack-Mounted Upss

    (2) Input circuit breaker (3) Universal serial bus (USB) port (security (4) RS232 port protection mechanism supported) (5) Smart SNMP card slot (optional) (6) External battery connector (only for long Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 14 UPS2000-(1 kVA-3 kVA) User Manual 2 Overview backup time models) (7) Output socket (C13) (8) Output terminal (connect to a 2.5mm power cable) Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 15: Installing The Ups

    3.2 Tools Get tools insulated to prevent electric shocks. Table 3-1 lists the tools that may be used during installation. Table 3-1 Tools Appearance, Specifications, and Name Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 16 PVC insulation tape Cotton cloth Brush Heat shrink tubing Heat gun Electrician's knife Protective gloves Electrostatic Insulation gloves Hydraulic pliers Cable tie discharge (ESD) gloves Pallet truck Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 17: Installing Ups2000-G

    Step 5 Place UPS on the support bases in sequence. Step 6 Adjust the UPS. Figure 3-2 Tower-mounting the UPS2000-G Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 18: Installing Cable And Starting Ups2000-G

    After routing cables, check that all cable connections are correct. Reinstall the small protective cover on the rear panel. Figure 3-4 Connecting cables to the 3KRTS UPS output Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 19 Step 3 Install the optional communication card to the UPS. For the installation procedure, See the RMS-SNMP01B V200R001 User Manual, RMS-RELAY01B V200R001 User Manual, RMS-MODBUS01B V200R001 User Manual. Figure 3-7 Installing an optional card on the 3KRTS UPS Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 20 Figure 3-9 Connecting communications cables to the 3KRTS UPS Figure 3-10 Connecting communications cables to the 3KRTL UPS  The USB channel supports a serial data communications protocol between the UPS and the PC. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 21 Figure 3-12 Connecting cables to the 3KRTL UPS input Step 6 Start the UPS. Hold down the ON/MUTE button on the front panel for 2 seconds to start the UPS. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 22 If you need to remotely monitor the UPS to understand the UPS and load running status and alarm information, install the UPS monitoring software on the PC and set UPS parameters. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 23: Installing Ups2000-A

    You are advised to use AWG14 power cables (with the cross-sectional area of 2.5 mm After routing cables, check that all cable connections are correct. Reinstall the small protective cover on the rear panel. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 24 Step 3 Install the optional communication card to the UPS. For the installation procedure, see the RMS-SNMP01B V200R001 User Manual, RMS-RELAY01B V200R001 User Manual, RMS-MODBUS01B V200R001 User Manual. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 25 Connect the UPS to the RS232 or USB port on a PC. Then you can monitor the UPS status using the PC as long as you have installed the monitoring software. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 26 ViewPower User Manual in the CD-ROM. Step 5 Connect the UPS input power cables. Take out input power cables from the fitting bag, and connect mains input power cables to the UPS. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 27 Hold down the ON/MUTE button on the front panel for 2 seconds to start the UPS. Figure 3-24 LCD display after the 3KRTS/3KRTL UPS starts Step 7 Set UPS Parameters Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 28: Installation Verification

    Cable connections for USB Cables to USB ports and ports and network ports network ports are connected correctly and securely. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 29 UPS input end. Distances between cable ties Distances between cable ties are the same, and no burr exists. Operating environment Clean the conductive air and other sundries. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 30: Setting Control Panel

    UPS, view the running status, set parameters, and view alarms. Figure 4-1 LCD panel Table 4-1 Icon description Icon Function Backup time Displays the remaining power backup time in digits. H: hour; M: minute; S: second Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 31 Displays that the UPS is in bypass mode Displays that the UPS is in ECO mode Indicates that the frequency conversion circuit is working Displays that the output socket is delivering power output Battery Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 32: Buzzer Alarm Tones

    Beeps twice every second. Error Buzzes continuously. Bypass mode Beeps once every 10 seconds. 4.3 Character Display Table 4-3 Character display description Acronym Display Description Enable Disable Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 33: Buttons

    Low voltage 4.4 Buttons The control panel provides three buttons to start and shut down the UPS, and view and set parameters. Table 4-4 describes the three buttons. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 34 UPS to enter the standby mode or bypass mode (if set or enabled before).  Confirming setting: During the setting of UPS parameters, press OFF/ENTER to Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 35: Setting Parameters

    UPS will not enter the bypass mode. 4.5 Setting Parameters There are ten configurable parameters on the LCD. The following figures show the parameter setting screens. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 36 The CF constant-frequency mode takes priority over the ECO mode. If the CF constant-frequency mode is enabled, the ECO mode cannot be enabled.  03: Enable or disable the bypass mode. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 37 0-999: Set the UPS battery capacity in the range of 0 Ah to 999 Ah. (The default setting for standard model is 9 Ah and for long backup time model is 7 Ah.) Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 38 The value range in is 7 V AC to 24 V AC. (The default setting is +12 V AC.)  10: Set the lowest allowable voltage in ECO mode. Display Setting Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 39: Operating Modes

    When the input voltage is abnormal or an outage occurs, the UPS transfers to battery mode. The buzzer beeps once every 4 seconds. The UPS uses batteries to supply power. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 40: Alarm Handling

    320 V. startup of the cleared. UPS. If this alarm is generated, the UPS fails to start. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 41 1.15 times the running of the cleared. rated output UPS, the UPS voltage. transfers to bypass mode. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 42 If this alarm persists, the UPS then transfers to no output again. After the UPS transfers to no output three times, the alarm needs to be manually cleared. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 43 When the cleared battery after the undervoltage alarm is transfers generated, the to battery mode. automatically transfers to normal mode and starts the charger for charging. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 44 If this alarm is generated three times within 3 hours, the UPS does not start or clear the fault. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 45: Alarm Trigger

    10 V when the charger has no output and the UPS inverter is started. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 46 Internal The ambient The UPS This alarm Minor overtem temperature remains in the perature exceeds 50º C. current state automatic and cannot ally start. cleared. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 47 Eeprom. restored to the automatic factory settings. ally If this alarm is cleared. generated, the customer needs to replace the UPS. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 48: Alarm Indication

    Beeps twice every second. Overheating Beeps once every second. Charger fault Beeps once every second. Bypass frequency unstable Beeps once every second. EEPROM error Beeps once every second. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 49: Troubleshooting

    UPS. loads are directly connected to the main power source. The error code is The UPS shuts down due to Remove surplus load from Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 50 TP exceeds the upper threshold. faulty, contact the dealer. and the buzzer buzzes Wait until the internal continuously. temperature drops, and then start the UPS. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 51: Maintenance And Storage

    Table 6-1 UPS charging during storage Storage Temperature Charge Interval Charge Duration –25° C to +40° C Three months 1–2 hours 40° C to 45° C Two months 1–2 hours Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 52: Routine Maintenance

    AC, 230 V AC, or 240 V whether an alarm is AC (single-phase input); present. 380 V AC, 400 V AC, or 415 V AC (three-phase Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 53: Quarterly Maintenance

    External cable and terminal Cables and terminals are Replace the cables. free from deterioration, Secure the output terminals. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 54: Semi-Yearly Maintenance

    Never use any organic solvent to clean batteries.  Never try to remove the safety valve or fill anything into batteries.  Never smoke or use fire around batteries. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 55: Monthly Maintenance

    The battery shell is intact, deformed parts and without acid leaks, faulty parts of batteries. deformation, or bulges. 2. Check and record the charge voltage and current of the battery Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 56: Quarterly Maintenance

    (over the LCD). 7.2.4 Yearly Maintenance Yearly maintenance tasks include quarterly maintenance tasks and the following:  Check for loose connections.  Discharge the battery string once a year. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 57: Specifications

    290 V AC (tolerance ± 5%, load percentage < 80%) recovery 270 V AC (tolerance ± 5%, 80% < load percentage < 100%) voltage Frequency range 40–70 Hz Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 58 Transfer Transferring time from normal mode to battery mode Bypass to 4 ms (100% R Load) ECO or ECO to bypass Waveform (battery mode) Sine wave Efficiency Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 59 Net weight 4.1 kg 6.7 kg 7.4 kg Environment Operating temperature 0–40° C –40° C to +70° C (Battery Package: –20° C to +40° C) Storage temperature Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 60: Rack-Mounted Ups Specifications

    (Ratio of actual load to rated load: 100%–80%/80%–70%/70%–60%/60%–0) Highest 300 V AC (tolerance ± 5%, load percentage < 80%) conversion 280 V AC (tolerance ± 5%, 80% < load percentage < voltage Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 61 Harmonic distortion ≤ 6% THD (non-linear load) Transfer Transferring time from normal mode to battery mode Bypass to ECO 4 ms (100% R Load) or ECO to Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 62 –40° C to +70° C (battery pack: –20° C to +40° C) Storage Temperature Altitude < 1000 meters Operating humidity 20–90 % RH @ 0–40° C (non-condensing) Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 63 Allows the administrator to manage the power over a web browser. In frequency conversion mode, if the output voltage is 200–208 V AC, the load should be derated to 80%. Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 64: Acronyms And Abbreviations

    Conformite Europeenne Economy Control Operation HTTP-Hypertext Transfer Protocol HTTP liquid crystal display Power Factor Correction RS232 Recommend Standard 232 SNMP Simple Network Management Protocol Total Harmonic Distortion Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 65 UPS2000-(1 kVA-3 kVA) User Manual A Acronyms and Abbreviations uninterruptible power system Issue 03 (2015-06-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.